Carrier High Wall Duct Free Split System 38MVC Service Manual page 34

Comfort series high-wall duct-free split system sizes 009 - 024
Hide thumbs Also See for High Wall Duct Free Split System 38MVC:
Table of Contents

Advertisement

CHART 9 - - UNIT NOT RUNNING OPTIMALLY (HP IN HEATING)*
Visually check outdoor
Visually check outdoor
Unit for ice blockage. **
Unit for ice blockage. **
Yes
Yes
Check defrost sensor. Ok?
Check defrost sensor. Ok?
Go to flow chart #2
Yes
Yes
Check application limits.
Check application limits.
Ok?
Ok?
Yes
Yes
Check ambient conditions.
Check ambient conditions.
Prime icing?
Prime icing?
Yes
Yes
Explain to customer
Explain to customer
* To supplement flow chart #8
** Check for blockage on outdoor coil and drain pan. Are the holes in drain pans blocked?
No
No
Check reversing valve.
Check reversing valve.
Go to flow chart #12
No
No
Replace sensor
Replace sensor
No
No
Beyond operating range
Beyond operating range
34
es in drain pans blocked?
A08184