Carrier High Wall Duct Free Split System 38MVC Service Manual page 33

Comfort series high-wall duct-free split system sizes 009 - 024
Hide thumbs Also See for High Wall Duct Free Split System 38MVC:
Table of Contents

Advertisement

CHART 8 - - UNIT NOT RUNNING OPTIMALLY
No
No
Outdoor coil clean?
Outdoor coil clean?
Yes
Yes
No
No
Indoor filter clean?
Indoor filter clean?
Yes
Yes
Check indoor fan
Check indoor fan
No
No
motor
motor
Yes
Yes
Connect gauges to
Connect gauges to
Yes
Yes
unit. Pressures ok?
unit. Pressures ok?
No
No
No
No
Suction and head
Suction and head
equal?
equal?
Yes
Yes
Check compressor
Check compressor
* Restriction in system. Check capillary tube, check for moisture, and check for damage to liquid line between indoor and
* Restriction in system. Check capillary tube, check for moisture, and check for damage to liquid line between indoor and
outdoor units.
outdoor units.
Clean coil. Problem
Clean coil. Problem
No
No
persists?
persists?
Yes
Yes
Clean filter. Problem
Clean filter. Problem
No
No
persists?
persists?
Yes
Yes
Replace indoor fan
Replace indoor fan
motor.
motor.
Check application
Check application
limits.
limits.
No
No
Normal suction,
Normal suction,
high head?
high head?
Yes
Yes
Non condensables
Non condensables
in sys. Pump down
in sys. Pump down
and recharge unit
and recharge unit
Problem solved
Problem solved
Problem solved
Problem solved
No
No
High head, high
High head, high
suction?
suction?
Yes
Yes
Unit is overcharged.
Unit is overcharged.
Reclaim charge and
Reclaim charge and
weigh in correct charge
weigh in correct charge
33
High head, low
High head, low
suction?
suction?
Yes
Yes
See note below*
See note below*
A08170