Executing commands - general procedure

5.7 Executing commands - general procedure
28
Building Technologies
Fire Safety
This chapter describes the general procedure of how to execute commands with
the service device, for example testing detectors or activating alarms. Commands
are basically executed in three steps:
1. Enter command on service device.
2. Transfer command to compatible device.
The three LEDs flash while the service device is searching for the
peripheral device.
The yellow and green LEDs flash while the service device is executing the
command.
The LEDs stop flashing once the command has been executed.
The command result is indicated by the LEDs.
3. Read result off LEDs and/or service device display. See table below and the
'Deviation list [
41]' chapter.
LEDs
Green
Green and yellow
Yellow
Yellow and red
Red
For more information about the results and corresponding measures, refer to
documentation for corresponding device.
The procedure is different for the following product groups:
Point detector [
29]
Manual call point [
Alarm sounder and alarm sounder with supplementary optical indication [
Input/output modules, linear smoke detector and radio gateway [
The detector line and software version of the fire control panel determine which
commands can be executed.
You will find further information in the 'Testing devices, activating alarms and test
alarms [
33]' chapter.
See also
Setup [
Meaning
Confirmation: Command was
successfully transferred.
OR
Test result: Device is ok.
Observe information on the display
Observe information on the display
Error, observe information on the display
Communication error, observe information
on the display
30]
16]
31]
32]
009718_e_en_--
2014-04-11