Testing device and activating test alarm

'2.3 Check+Testalarm' menu
The device is initially tested with the '2.3 Check+Testalarm' command. If there are
no deviations and the device is in test mode, a test alarm is activated.
NOTICE
Danger of alarms on collective, MS8, interactive, AnalogPLUS, and SIGMALOOP
detector lines
On collective, MS8, interactive, AnalogPLUS, and SIGMALOOP detector lines, an
alarm is activated instead of a test alarm as only the peripheral device is used in
test mode. The information confirming that the peripheral device is in test mode is
not sent to the fire control panel.
Take appropriate alarm evaluation measures before executing this command.
1. Switch the device to test mode on the control panel.
2. Execute the '2.3 Check+Testalarm' command.
The device is tested.
If there is no deviation and the device is in test mode, a test alarm is
activated.
If the device is not in test mode, this is indicated by the LEDs and on the
display. In this instance, a test alarm is not activated.
If there is a deviation, this is indicated by the LEDs and on the display. In
this instance, a test alarm is not activated.
3. Switch the device back to normal mode on the control panel.
You will find more information about switching the test mode on and off in the
documentation for the fire detection system.
See also
Executing commands - general procedure [
Deviation list [

Activating danger level 2

'2.10 WARNING DL2' menu
You can activate danger level 2 with the '2.10 WARNING DL2' command.
NOTICE
Danger of alarm due to incorrect use
If you activate danger level 2, an alarm can be activated on the control panel.
Take appropriate alarm evaluation measures before executing this command.
Firmware version 2.6 or higher is installed on the service device.
Execute the '2.10 WARNING DL2' command.
Danger level 2 is activated.