KROHNE OPTISWIRL 4200 Series Supplementary Instructions Manual

KROHNE OPTISWIRL 4200 Series Supplementary Instructions Manual

Vortex flowmeter
Hide thumbs Also See for OPTISWIRL 4200 Series:

Advertisement

OPTISWIRL 4200
OPTISWIRL 4200
OPTISWIRL 4200
OPTISWIRL 4200
Vortex flowmeter
Equipment category II 2G and II 2D, EPL Gb and Db
in protection type Flameproof enclosure Ex-d and
in protection type Increased safety Ex-e and
in protection type Equipment - dust ignition protection through enclosure Ex-t
© KROHNE 08/2016 - 4005002601- AD OPTISWIRL4200 Ex-II2GD R01 en
Supplementary Instructions
Supplementary Instructions
Supplementary Instructions
Supplementary Instructions

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the OPTISWIRL 4200 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for KROHNE OPTISWIRL 4200 Series

  • Page 1 Equipment category II 2G and II 2D, EPL Gb and Db in protection type Flameproof enclosure Ex-d and in protection type Increased safety Ex-e and in protection type Equipment - dust ignition protection through enclosure Ex-t © KROHNE 08/2016 - 4005002601- AD OPTISWIRL4200 Ex-II2GD R01 en...
  • Page 2: Table Of Contents

    4.5 Flow sensor circuits (remote version only) ..............22 5 Operation 5.1 Start-up........................... 23 5.2 Operation ........................23 5.3 Electrostatic charge ....................... 23 6 Service 6.1 Maintenance ........................24 6.2 Dismantling ........................24 7 Notes www.krohne.com 08/2016 - 4005002601- AD OPTISWIRL4200 Ex-II2GD R01 en...
  • Page 3: Safety Instructions

    The "X" after the certificate number refers to special conditions for safe use of the device, which have been listed in these instructions. If needed, the IEC certificate can be downloaded from the manufacturer's website. 08/2016 - 4005002601- AD OPTISWIRL4200 Ex-II2GD R01 www.krohne.com...
  • Page 4: Safety Instructions

    Assembly, installation, start-up and maintenance may only be performed by personnel trained in explosion protection! CAUTION! Operating conditions and place of installation may require compliance with additional standards, directives or laws. The responsibility for compliance rests solely with the operator or his agent. www.krohne.com 08/2016 - 4005002601- AD OPTISWIRL4200 Ex-II2GD R01...
  • Page 5: Device Description

    * positions which are not needed are omitted (no blank positions) The remote version consisting of the flow sensor OPTISWIRL 4000 and the signal converter VFC 200 F 020 is called the OPTISWIRL 4200 F. 08/2016 - 4005002601- AD OPTISWIRL4200 Ex-II2GD R01 www.krohne.com...
  • Page 6: Marking

    5 Marking acc. to KIWA 14 ATEX 0016 X or IECEx KIWA 15.0021 X 6 Permissible ambient temperature range 7 Electrical connection data 8 Observe the safety instructions 9 Internet address of the manufacturer www.krohne.com 08/2016 - 4005002601- AD OPTISWIRL4200 Ex-II2GD R01...
  • Page 7: Flammable Products

    Definition of zone 21 acc. to EN 1127-1, Appendix B: An area in which an explosive atmosphere may occasionally occur in the form of a cloud of flammable dust in the air under normal operation. 08/2016 - 4005002601- AD OPTISWIRL4200 Ex-II2GD R01 www.krohne.com...
  • Page 8: Protection Types

    C Db C Db Ex ia IIIC T70 Ex ia IIIC T70°C...T240 Ex ia IIIC T70 Ex ia IIIC T70 C...T240 C...T240 C...T240°C Db C Db C Db (flow sensor) C Db www.krohne.com 08/2016 - 4005002601- AD OPTISWIRL4200 Ex-II2GD R01...
  • Page 9: Ambient Temperature / Temperature Classes

    The classification is outlined in the following tables. The tables take into account the following parameters: • Ambient temperature T • Product temperature T • Nominal size DN • Heat resistance of the connecting cable 08/2016 - 4005002601- AD OPTISWIRL4200 Ex-II2GD R01 www.krohne.com...
  • Page 10 The minimum product temperature is -40°C / -40°F. When using in zone 21, observe the maximum permissible product and ambient temperatures for temperature class 2 and the information for use of a heat-resistant connecting cable and cable entry. www.krohne.com 08/2016 - 4005002601- AD OPTISWIRL4200 Ex-II2GD R01...
  • Page 11 Temperature class in °F 140 149 140 Nominal size DN15…25 392 392 DN40…50 392 347 DN65…100 392 302 DN150...300 392 365 1 Permanent service temperature of connecting cable and cable entry min. 176°F 08/2016 - 4005002601- AD OPTISWIRL4200 Ex-II2GD R01 www.krohne.com...
  • Page 12 °F 140 149 140 149 140 Nominal size DN15…25 392 392 DN40…50 392 392 DN65…100 392 392 DN150...300 392 392 1 Permanent service temperature of connecting cable and cable entry min. 176°F www.krohne.com 08/2016 - 4005002601- AD OPTISWIRL4200 Ex-II2GD R01...
  • Page 13 Temperature class in °F 140 149 Nominal size DN15…25 248 248 DN40…50 248 239 DN65…100 248 221 DN150...300 248 248 1 Permanent service temperature of connecting cable and cable entry min. 176°F 08/2016 - 4005002601- AD OPTISWIRL4200 Ex-II2GD R01 www.krohne.com...
  • Page 14: Surface Temperature For Equipment Category Ii 2 D

    T70°C at an ambient temperature of 65°C / 149°F and a product temperature of 65°C / 149°F is valid without a dust coating. For higher product temperatures the maximum surface temperature is defined by the product. www.krohne.com 08/2016 - 4005002601- AD OPTISWIRL4200 Ex-II2GD R01...
  • Page 15: Electrical Data

    Piezo / Temperature sensor circuit (connector X2.7...X2.12) • U = 6.65 V • I = 21 mA • P = 35 mW • C = 2.6 µF • L = 0.5 mH 08/2016 - 4005002601- AD OPTISWIRL4200 Ex-II2GD R01 www.krohne.com...
  • Page 16 Remote circuit (connector X5501) Remote circuit (connector X5501) • U = 6.65 V • I = 1107 mA • P = 650 mW • C = 2.5 µF • L = 73 µH www.krohne.com 08/2016 - 4005002601- AD OPTISWIRL4200 Ex-II2GD R01...
  • Page 17: Installation

    • Loosen the hexagon socket screw 1. • Turn the signal converter or connection box. • Screw signal converter or connection box back to the base again. 1 Allen screws M4 on connection housing 08/2016 - 4005002601- AD OPTISWIRL4200 Ex-II2GD R01 www.krohne.com...
  • Page 18: Special Conditions

    The housing must be replaced if there is any damage to the joint area. The flameproof threads and the cylindrical joint between the terminal and the electronics compartments must be inspected visually after opening. www.krohne.com 08/2016 - 4005002601- AD OPTISWIRL4200 Ex-II2GD R01...
  • Page 19: Electrical Connections

    • Supplied blind plugs / cable entries guarantee protection against foreign objects and water (protection category) IP66 / 67 according to EN 60529. • The outer diameter of the connecting cable must be within the sealing range of the cable entry (7...12 mm / 0.27...0.47"). 08/2016 - 4005002601- AD OPTISWIRL4200 Ex-II2GD R01 www.krohne.com...
  • Page 20: Power Supply

    • All connecting cable conductors and shields that are not securely connected to the equipotential grounding system of the hazardous area shall be carefully isolated from each other and from ground (test voltage 1500 V for non-intrinsically safe cables). www.krohne.com 08/2016 - 4005002601- AD OPTISWIRL4200 Ex-II2GD R01...
  • Page 21: Grounding And Equipotential Bonding

    For remote systems the connection of the flow sensor can either be made via the PA connection in the signal converter terminal compartment or via the external PA connection. Ground connection remote version 1 Electrical grounding connection on measuring sensor 2 Electrical grounding connection on signal converter housing 08/2016 - 4005002601- AD OPTISWIRL4200 Ex-II2GD R01 www.krohne.com...
  • Page 22: Flow Sensor Circuits (Remote Version Only)

    4 Filler wire pair shielding (protected with heat shrink tubing) 5 Fork clamp pair shielding on signal converter side 6 Heat shrink tubing The flow sensor circuit is designed in protection type intrinsically safe Ex ia II C. www.krohne.com 08/2016 - 4005002601- AD OPTISWIRL4200 Ex-II2GD R01...
  • Page 23: Operation

    • spraying of electrons (e.g. in the vicinity of electrostatic painting systems) or • pneumatically conveyed dust is exposed. CAUTION! Electrostatic charging of the housing surface by friction must be avoided. The devices must not be dry cleaned. 08/2016 - 4005002601- AD OPTISWIRL4200 Ex-II2GD R01 www.krohne.com...
  • Page 24: Service

    The display can be rotated in 90° increments. It is connected to the connector as shown in the following figure. Exchanging the converter insert It is permitted to replace the entire VFC 200 converter insert with a version identical in construction. www.krohne.com 08/2016 - 4005002601- AD OPTISWIRL4200 Ex-II2GD R01...
  • Page 25 In the case of environmentally critical or hazardous products, appropriate safety precautions • must be taken with regard to residual liquids in the measuring unit. New gaskets have to be used when re-installing the device in the piping. • 08/2016 - 4005002601- AD OPTISWIRL4200 Ex-II2GD R01 www.krohne.com...
  • Page 26: Notes

    NOTES OPTISWIRL 4200 www.krohne.com 08/2016 - 4005002601- AD OPTISWIRL4200 Ex-II2GD R01...