Terminal Assignment Of The Di 8×24 - Siemens SIMATIC 6DL1131-6DF00-0PK0 Equipment Manual

Table of Contents

Advertisement

Terminal
5.1 Terminal assignment
Description
The pin assignment is made as follows:
Table 5-1
Terminal assignment of the DI 8×24...125VDC HA
Terminal
Assignment
1
DI
0
3
DI
2
5
DI
4
7
DI
6
9
2M
11
2M
13
2M
15
2M
1P1
L+
2P1
L+
Notice
Note differences in potential
The load voltage supply and the signal voltage of the I/O module are electrically isolated.
The connection of the load supply voltage and the signal voltage is only permissible when no compensating currents are
flowing as a result of a difference in potential.
The connection of additional, external devices to terminals with the assignment 2M is not permissible. The additional load
may result in the destruction of the I/O module as well as further faults.
16
Terminal
Assignment
2
DI
1
4
DI
3
6
DI
5
8
DI
7
10
2M
12
2M
14
2M
16
2M
1P2
M
2P2
M
Explanations
DI
: Input signal, channel n
n
2M: Signal voltage
1P1: Supply voltage L+ of the voltage bus 1P
2P1: Supply voltage L+ of the voltage bus 2P
1P2: Ground reference of the voltage bus 1P
2P2: Ground reference of the voltage bus 2P
1 DI.0+
DI
2
DI.1+
3 DI.2+
4
DI.3+
5 DI.4+
DI.5+
6
7 DI.6+
DI.7+
8
9
2M
10
11
12
13
14
15
16
1P1 L+ 24VDC
M 1P2
2P1 L+ 24VDC
M 2P2
MAX. 10 A
Equipment Manual, 10/2021, A5E39288633-AD
DI 8x24...125VDC HA

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic 6dl1131-6df00-0ek0Simatic et 200sp ha6dl1131-6df00-0pk06dl1131-6df00-0ek0

Table of Contents