Interval Function; Collector Frost Protection; Extended Functions; Additional Function For Dhw Heating - Viessmann SDIO/SM1A Installation And Service Instructions Manual

Table of Contents

Advertisement

Version with SM1 and KM-BUS

Interval function

Set code/parameter "07:1".
Activate the interval function in systems where the col-
lector temperature sensor is not in an ideal location, to
prevent a time delay in capturing the collector temper-
ature.

Collector frost protection

Viessmann collectors are filled with Viessmann heat
transfer medium. Consequently, this function does not
need to be enabled.
Only enable it if water is used as the heat transfer
medium.

Extended functions

The extended functions are set in coding address "20".

Additional function for DHW heating

With the additional function for DHW heating (boiler
circuit control unit function), the solar preheat stage
can be heated at the selected times.
Boiler control unit settings:
Set a 2nd set DHW temperature in coding address
"58" or parameter "03" ("DHW" group).
Activate a 4th DHW phase for DHW heating.
Set the additional function (in conjunction with the
required further function) in coding address "20"
("Solar" group).

Differential temperature control 2

Set code/parameter "20:2" or "20:3".
If the temperature captured by temperature sensor
is higher by a value equal to the selected start/stop
temperature differential (coding address "22" and "23")
than the temperature captured by temperature sensor
, then output
will be 'live'.
sS
(cont.)
To prevent damage to the collectors, the solar circuit
pump is switched on if the collector temperature falls
below +5 °C. The pump is stopped when a tempera-
ture of +7 °C is reached.
See coding address "0B".
Note
Extended control functions can be used only in relation
to the selected system example and the system com-
ponents listed there.
Note
In coding address "56" or parameter "01" ("DHW"
group), the setting range for the DHW set temperature
can be adjusted to between 10 and over 60 °C.
This signal is then relayed via the KM-BUS/PlusBus to
the SDIO/SM1A electronics module. The de-stratifica-
tion pump starts.
/
Function description
25