Incorrect Circulation In The Solar Circuit - Viessmann SDIO/SM1A Installation And Service Instructions Manual

Table of Contents

Advertisement

Repairs
(cont.)
100
10
1
0.1
0
20
25
40
Temperature in °C
Fig. 3
A
Collector temperature sensor
NTC 20 k
)
Ω
Cylinder temperature sensor
B
Temperature sensor
Temperature sensor
(sensor type: NTC 10 k

Incorrect circulation in the solar circuit

If code/parameter "0D:1" has been set (delivered con-
dition), unwanted DHW circulation (e.g. at night) is
captured. In "Diagnosis solar" (weather-compensa-
ted control unit) or "Brief scan" (constant temperature
control unit), the number of instances where incorrect
circulation was captured can be scanned.
B
60
80
100
&
(sensor type:
%
/
)
Ω
A
120
140
Check time shown at the control unit; adjust if neces-
sary.
Check current collector temperature and cylinder
temperature via diagnosis.
If the collector temperature is too low and the cylin-
der temperature too high, then the sensors have
been interchanged.
Switch off all actuators via a relay/actuator test.
If the solar circuit pump continues to run, see "Check
solar circuit pump at output
If the flow and return temperature rises when the
solar circuit pump is switched off, there may be re-
circulation via gravity.
Check any installed check valves or install them if
necessary.
Troubleshooting
".
sF
17