Cleaning

Care, inspection and maintenance

The inspection and maintenance of heating systems is
prescribed by the Energy Saving Ordinance [in Ger-
many], EN 806 and DIN 1988-8 (
8131).
Regular maintenance ensures trouble-free, energy effi-
cient and environmentally responsible heating. For
this, we strongly advise you to arrange an inspection
and maintenance contract with your heating contractor.
Boiler
Increasing boiler contamination raises the flue gas
temperature and thereby increases energy losses. As
well as observing the cleaning intervals specified, the
boiler must therefore also be thoroughly cleaned once
a year.

Information on cleaning

Danger
Hot surfaces can lead to serious injuries.
Only open the boiler after it has cooled down.
Carry out the cleaning at the specified intervals.
Only clean the boiler with the cleaning equipment
provided, a spatula or scraper, and a vacuum
cleaner.
Never use chemical cleaning agents.
Have a heating contractor clean the boiler com-
pletely once a year (see following table).

Cleaning intervals (overview)

Vitoligno 200-S
After every approx. 25 hours run
Remove ash from ash chamber, combustion chamber and
hopper
After every approx. 50 hours run
Clean ash chamber, hopper and doors
Check system pressure
After every approx. 350 hours run
Clean flue gas fan, secondary heating surfaces, turbulators
and flue gas collector
Clean Lambda probe
Every 3 years
Maintenance of moving parts (shafts, bearings, etc.)
Every 5 years
Replace the battery inside the control unit
: ÖNORM B
a
Safety valve
Check the safety valve function every six months by
venting, or have it checked by your heating contractor.
The valve seat may become contaminated (see the
valve manufacturer's instructions).
Thermally activated safety valve
Check the availability of the thermally activated safety
valve every year by venting, or have it checked by your
heating contractor. The valve seat may become conta-
minated (see the valve manufacturer's instructions).
Note
The following cleaning intervals are intended as a
guide that can be adapted, if required, to the fuel qual-
ity and operating conditions.
!
Please note
There is a risk of fire and burns due to hot cin-
ders.
Wear suitable safety gloves.
Only dispose of the hot ash in fireproof con-
tainers with covers.
System user
X
X
X
Maintenance and cleaning
Heating contractor
X
X
X
X
45