Allen-Bradley DC-UPS Manual page 30

Table of Contents

Advertisement

DC-UPS - 24V, 20 A, 480 W Reference Manual
30
Sensor Board for DC-UPS
1606-XLSBATSEN enables the benefits of the 1-Battery-Concept when using
individual batteries and not one of the battery modules. This sensor board
makes the use of matched batteries unnecessary and allows a precise battery
charging and testing resulting in the longest possible battery life. The sensor
board contains a PT1000 temperature sensor and an auto-resettable fuse that
is suitable for charging currents up to 3.5 A. The fuse protects the center-tap
wire between the battery module and the DC-UPS control unit.
24V, 12AH Battery Module - 1606-XLSBATASSY3
The 1606-XLSBATASSY3 passive battery module utilizes two maintenance-free
7Ah lead-acid batteries (connected in series), that are assembled in one
package with all required wiring included.
The battery module includes the monitoring and protection board 1606-
XLSBATSEN. This board contains a temperature sensor and a center-tap
connection with an auto-resettable fuse to protect the center-tap wire between
the battery module and the DC-UPS control unit. Connecting the center-tap
wire to the DC-UPS control unit enables all benefits of the 1-Battery-Concept.
This makes the use of matched replacement batteries unnecessary and allows a
precise battery charging and testing which results in the longest possible
battery life.
The battery module is available in two different options. It can be ordered with
assembled batteries (1606-XLSBATASSY3) or as a battery bracket without
batteries (1606-XLSBATBR3), allowing for different battery options. The
mounting bracket option also allows the batteries to be assembled just in time,
avoiding outdated batteries due to limited shelf life.
Attribute
Battery voltage
Battery capacity
Temperature sensor
Dimensions W x H x D
Weight 1606-XLSBATASSY3 / 1606-XLSBATBR3
1606-XLSBATASSY4
The 1606-XLSBATASSY4 passive battery module utilizes two maintenance-free
12 Ah VRLA lead-acid batteries (connected in series), that are assembled in one
package with all required wiring included.
The battery module includes the monitoring and protection board 1606-
XLSBATSEN. This board contains a temperature sensor and a center-tap
connection with an auto-resettable fuse to protect the center-tap wire between
the battery module and the DC-UPS control unit. Connecting the center-tap
wire to the DC-UPS control unit enables all benefits of the 1-Battery-Concept.
This makes the use of matched replacement batteries unnecessary and allows a
Rockwell Automation Publication 1606-RM008A-EN-P - November 2021
Value
DC 24V
7Ah
PT1000
137 x 186 x 143 mm (5.39 x 7.32 x 5.63 in.)
6000 g / 800 g (13.23 lb / 1.76 lb)