Electromagnetic Compatibility - Allen-Bradley DC-UPS Manual

Table of Contents

Advertisement

Electromagnetic
Compatibility
The DC-UPS is suitable for applications in industrial environment and in
residential, commercial, and light industry environment without any
restrictions.
All tests are performed in power supply and battery mode.
Attributes
(2)
Electrostatic discharge
Electromagnetic RF field
Fast transients (Burst)
Surge voltage on input
Surge voltage on output
Surge voltage on battery
and center-tap
Surge voltage on inhibit
input, ready-, buffering and
replace battery contacts
Surge voltage on
temperature sensor
Conducted disturbance
(1) Criterion A: The device shows normal operation behavior within the defined limits.
Criterion B: The device operates continuously during and after the test. During the test, minor temporary
impairments may occur. If they do occur, the device corrects them.
Criterion C: Temporary loss of function is possible. The device may shut down. If it shuts down, it then restarts by
itself. No damage or hazards for the device occur.
(2) Chassis ground connection earthed (grounded)
(3) Tested with coupling clamp
(4) Not relevant due to short wire length
Rockwell Automation Publication 1606-RM008A-EN-P - November 2021
Standards
Values
Contact discharge
EN 61000-4-2
Air discharge
EN 61000-4-3
80 MHz...2.7 GHz
Input lines
Output lines
EN 61000-4-4
(3)
Signals
L  N
EN 61000-4-5
N / L  PE
+  -
EN 61000-4-5
+ / -  PE
+  -
EN 61000-4-5
+ /-chassis ground
signals  chassis
EN 61000-4-5
ground
signals  chassis
EN 61000-4-5
ground
EN 61000-4-6
0.15...80 MHz
DC-UPS - 24V, 20 A, 480 W Reference Manual
(1)
Criteria
8 kV
Criterion A
15 kV
Criterion A
10V/m
Criterion A
2 kV
Criterion A
2 kV
Criterion A
2 kV
Criterion A
1 kV
Criterion A
2 kV
Criterion A
1 kV
Criterion A
2 kV
Criterion A
(4)
Criterion A
1 kV
Criterion A
1 kV
Criterion A
1 kV
Criterion A
10V
Criterion A
23