DC-UPS - 24V, 20 A, 480 W Reference Manual
24V Power
8
Use a 4 A fuse (ATOF® 287 004 from Little fuse or an UL Listed fuse with
same characteristics) between the connection point of the two 12V
batteries and the "Center Tap" connection point of the DC-UPS. An
equivalent protection is included on the original battery modules. The
center tap connection is not mandatory but enables an individual
charging and monitoring of the two batteries.
Optionally, a PT1000 temperature sensor can be connected to terminals
point 11 and 12 to measure the battery temperature. This adjusts the
charging voltage according to the battery temperature, which extends
the battery life. This sensor is already installed in the original battery
modules.
Installation Instructions for Hazardous Location Areas
The device is suitable for use in Class I Division 2 Groups A, B, C, D
locations and for use in Group II Category 3 (Zone 2) environments.
Hazardous Location Classification: ATEX: EPS 15 ATEX 1 025 X, II 3G EX
EC nC IIC T4 Gc
WARNING: Explosion Hazards
• Substitution of components may impair suitability for this environment.
• Do not disconnect the device or change unit settings unless power has been
• A suitable enclosure must be provided for the end product, which has a
Figure 1 - Typical Wiring Diagram
-
-
-
DC
Input
Output
Output
Battery
-
Center Tap
AC
Input
Temp. Sensor
N
L PE
DC-UPS
Supply
Rockwell Automation Publication 1606-RM008A-EN-P - November 2021
switched off or the area is known to be non-hazardous.
minimum protection of IP54 and, fulfills the requirements of the EN 60079-
-
Bat1
12V
Buffered
buffered
Load
Bat2
12V
Temp.
Sensor
24V Battery
Module
24 V
Non-bufferd
branches
24V
buffered
branches
-
Non-
Load