Error Handling - KROHNE OPTIFLEX 1300 C Handbook

Guided radar (tdr) level meter
Hide thumbs Also See for OPTIFLEX 1300 C:
Table of Contents

Advertisement

OPERATION
6
The time since the error occured is measured in Days:Hours:Minutes:Seconds
the time when the instrument is energized. The error is saved in the memory of the instrument
when it is switched off. The counter continues when the instrument is switched back on.
The error symbol is no longer displayed after you read the error record.

6.6.2 Error handling

Types of error message
Type of error
Error
Warning
Description of errors and corrective actions
Error Message
Current output
Current output saturated at
maximum value.
Current output saturated at
minimum value.
External influences
Temperature is out of range
for NAND Flash
Self-test manager
Self Test has failed
104
Days:Hours:Minutes:Seconds
Days:Hours:Minutes:Seconds
Days:Hours:Minutes:Seconds. It only includes
Error
code
Description
E
If an error message is displayed in the error record (menu
item B.2.12), the measured value is not correct. The output
current goes to the value set in menu items C.3.5 Error
Handling (Ouput 1) and C.4.5 Error Handling (Output 2). For
more data about the menu items, refer to
on page 77.
W
If a warning message continues, the measured value will no
longer be correct.
Error
code
Description
W
The output is at its maximum
output value (20 or 20.5 mA)
because the measured value
is now out of the
measurement range.
W
The output is at its minimum
output value (4 or 3.8 mA)
because the measured value
is now out of the
measurement range.
W
The ambient temperature is
outside the given range. This
can cause loss or corruption
of data.
E
The instrument did not self-
test correctly.
www.krohne.com
OPTIFLEX 1300 C
C. Advanced setup
Corrective action
Fill the tank or remove some
of the product until the level
is back in the configured
range.
Fill the tank or remove some
of the product until the level
is back in the configured
range.
Switch off the instrument
until the ambient
temperature is back in the
given range. If the problem
continues, contact the
supplier.
Contact the supplier.
01/2008 • 4000172301 - HB OPTIFLEX 1300 R02 en