(b) LOGTRGR
• This instruction resets the LOGTRG instruction of the specified data logging setting No. Execution of the
LOGTRGR instruction enables the LOGTRG instruction of the specified trigger logging setting No.
• When this instruction is executed, the special relay (Data logging end, Data logging trigger, and After data
logging trigger) of the data logging setting No.n turns off.
• If this instruction is executed while data in the buffer is being saved to the SD memory card, processing of
the instruction does not start until completion of the data saving.
(2) Error
In the following case, an operation error occurs. The error flag (SM0) turns on, and an error code is stored into
SD0.
• When n is other than 1 to 10 (Error code: 4100)
(3) Program example
In the program shown below, when X0 turns on, the LOGTRG instruction is executed to data logging setting No.1.
And, when X1 turns on, the trigger condition is reset by the LOGTRGR instruction.