Emc - Pepperl+Fuchs PS1000-A6-12.16 Technical Information

Table of Contents

Advertisement

Power Supply PS1000-A6-12.16

EMC

18
EMC
The power supply is suitable for applications in industrial environments as well as
in residential, commercial and light industry environments.
EMC Immunity
Electrostatic discharge
Electromagnetic RF field
Fast transients (Burst)
Surge voltage on input
Surge voltage on output
Surge voltage on Signals EN 61000-4-5
Conducted disturbance
Mains voltage dips
Voltage interruptions
Voltage sags
Powerful transients
Criterion A
Power supply shows normal operation behavior within the defined limits.
Criterion C
Temporary loss of function is possible. Power supply may shut-down and restarts by itself.
No damage or hazards for the power supply will occur.
EMC Emission
Conducted emission
input lines
Conducted emission
1
output lines
Radiated emission
Harmonic input current
Voltage fluctuations, flicker EN 61000-3-3
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2)
this device must accept any interference received, including interference that may cause undesired operation.
1
For information only, not mandatory for EN 61000-6-3.
2
Tested with constant current loads, non pulsing.
26
According to generic standards: EN 61000-6-1 and EN 61000-6-2
EN 61000-4-2
Contact discharge
Air discharge
EN 61000-4-3
80MHz-2.7GHz
EN 61000-4-4
Input lines
Output lines
DC-OK signal (coupling clamp)
Shut-down input
EN 61000-4-5
L
N
L
PE, N
EN 61000-4-5
+
+ / –
PE
DC-OK signal
Shut-down input
EN 61000-4-6
0.15-80MHz
EN 61000-4-11
0% of 100Vac
40% of 100Vac
70% of 100Vac
0% of 200Vac
40% of 200Vac
70% of 200Vac
EN 61000-4-11
0% of 200Vac (=0V)
SEMI F47 0706
Dips on the input voltage according to SEMI F47 standard
80% of 120Vac (96Vac)
70% of 120Vac (84Vac)
50% of 120Vac (60Vac)
VDE 0160
Over entire load range
According to generic standards: EN 61000-6-3 and EN 61000-6-4
EN 55011, EN 55015, EN 55022,
FCC Part 15, CISPR 11,
CISPR 22
IEC/CISPR 16-1-2,
IEC/CISPR 16-2-1
EN 55011, EN 55022
EN 61000-3-2
8kV
15kV
20V/m
4kV
2kV
2kV
2kV
2kV
PE
4kV
1kV
2kV
PE
1kV
PE
1kV
20V
0Vac, 20ms
40Vac, 200ms
70Vac, 500ms
0Vac, 20ms
80Vac, 200ms
140Vac, 500ms
5000ms
1000ms
500ms
200ms
750V, 0.3ms
Class B
Limits for DC power port according
EN 61000-6-3 fulfilled
Class B
Class A fulfilled between 0A and 19.2A load
Class C fulfilled between 10A and 19.2A
load
2
Fulfilled
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion C
Criterion C
Criterion A
Criterion A
Criterion A
Criterion C
Criterion A
Criterion A
Criterion A
Criterion A

Advertisement