Installation
3
Installation
3.1
Incoming acceptance, storage
• Incoming acceptance:
Check the packaging and the device for damage. Check that the goods delivered are complete
and nothing is missing.
• Storage:
Storage temperature -40...+85 °C (-40 to +185 °F)
3.2
Installation instructions
For typical possibilities for installing the Ceraphant T - see the diagram below:
• Pressure measurement in gases (left)
Mount Ceraphant T with shut-off assembly above the sampling nozzle so that any condensate
can drain off into the process.
• Pressure measurement in steam (centre)
Mount Ceraphant T with U-pipe below the sampling nozzle. Fill the U-pipe with fill fluid
before commissioning.
• Pressure measurement in liquids (right)
Mount Ceraphant T below or at the same level as the sampling nozzle.
Fig. 2: Possibilities for installing to measure pressure in gases, steam and liquids.