Veris Industries HW2 Series Installation Manual page 6

Wall mount humidity sensors
Table of Contents

Advertisement

HW2 Protocol Series Installation Guide
Installation (cont.)
Z207936-0E
Page 6 of 11
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
32-Bit Holding Registers (Read/Write):
Register
Description
1
Temperature setpoint
3
Humidity setpoint
5
Screen color set
7
Device name
40
Fan speed
Note: All holding registers are preserved during power outages.
Coils (Read/Write):
Register
Description
3*
Touchbutton disable
5*
Temperature (°C)
6
Occupancy override
7*
Touch timeout
8*
Display shows humidity
12*
Display shows temperature setpoint on main screen
*Preserved during power outages.
BACnet Descriptions
Note: In the tables below, all properties are read-only unless otherwise noted. "Preserved" means the value is maintained
through power outages.
Present_Value Range Restrictions:
Object Name
DEV - Object_Name
Temperature Setpoint
Min_Pres_Value
Max_Pres_Value
Humidity Setpoint
Min_Pres_Value
Max_Pres_Value
Screen Color
Fan Speed
Device_Instance
Standard Object Types Supported:
Object Type
Analog Input - AI
Analog Value - AV
Binary Value - BV
Multistate Value - MSV
Device - DEV
©2021 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
Minimum Value
Maximum Value
1 Character
65 Characters
Min_Pres_Value
Max_Pres_Value
0
Max_Pres_Value -1
Min_Pres_Value +1
50
Min_Pres_Value
Max_Pres_Value
0
Max_Pres_Value -1
Min_Pres_Value +1
100
1
4
1
5
0
4,194,302
Supported Optional Properties
Writable Properties
Reliability
None
Min_Pres_Value
Min_Pres_Value
Max_Pres_Value
Max_Pres_Value
Present_Value
None
Present Value
None
Present Value
Max Info Frames
APDU_Timeout
Max_Master
Max_Master
Object_Name
0921