HW2 Protocol Series Installation Guide
Installation (cont.)
Z207936-0E
Page 4 of 11
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
CONTROL SYSTEM
RS-485 (+)
RS-485 (-)
COMMON
POWER SUPPLY 20-30 Vdc, 24 Vac
COMMON
-
POWER (+24)
+
5 4 3 2 1
6. Configure the device.
Address Configuration:
Each device on a single network must have a unique address. Set the DIP switch labeled "ADDRESS" to assign a unique address
before the device is connected to the network. If an address is selected that conflicts with another device, neither device will be
able to communicate.
Address the device as any whole number between and including 1 to 127. Note that zero is not a valid address for Modbus;
zero is a valid address for BACnet. Positions 1 through 7 of the "ADDRESS" DIP switch designate the address. Position 8 toggles
between the Modbus and BACnet communication protocols, as shown in the diagram below. This is the left bank of DIP
switches on the sensor.
Binary Address
LSB
2
4
16
32
1
8
Decimal Values
To set an address using the DIP switch, simply add the values of any switches that are in the ON position.
For example, an address of 73 is set as shown in the diagram below.
LSB
1
2
4
8
16
32
Position number 1 has an ON value of 1, position number 4 has an ON value of 8 and position number 7 has an ON value of 64 (1
+ 8 + 64 = 73).
©2021 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
MSB
64
Modbus/BACnet
Toggle
On = Modbus
O = BACnet
73
=