Detected Errors
If a communication error is detected, an Error Screen will
appear.
• All units In Service remain in the In Service position.
• All units in Standby go to In Service.
• Any unit in Regeneration when the error occurs
completes Regeneration and goes to In Service.
• No units are allowed to start a Regeneration Cycle while
the error condition exists, unless they are manually forced
into Regeneration.
• When an error is corrected and the error no longer
displays (it may take several seconds for all of the units
in a system to stop displaying the error message), the
system returns to normal operation.
NOTE: During the error condition, the control continues
to monitor the flow meter and update the volume
remaining. Once the error condition is corrected, all
units return to the operating status they were in prior
to the error. Regeneration queue is rebuilt according
to the normal system operation. Or, if more than
one unit has been queued for regeneration, then the
queue is rebuilt according to which one communicates
first.
Message Displayed
Error
Valve Count Mismatch
Motor Stall
No Changes Detected in the Optical
Sensor for 6 Seconds
Motor Run-On
No CAM Switch Change Detected
Optical Sensor
Undesired change detected by the
Optical Sensor
Over-Current
Motor Over-Current is Detected
Flow Meter Error
Continuous Flow Detected
Error
Send/Receive Failure
Error
System Type Mismatch on Network
Microcontroller Error
100 Days Without Regen
Cause For Error
Number of NXT2 detected does not match selected system
type in Master Programming
The motor is on but no encoder pulses are detected within a
given duration while homing.
The motor is on but no encloder pulses are detected or CAM
Switches change state within a given duration.
The motor is off but additional encoder pulses are detected.
Motor current exceeds thresholds.
Flow exceeded specified threshold for a specific duration.
During a setting push, a packet was missing.
The system type among connected units does not match.
Calibration or manufacturing test was not performed
100 Days have expired without a regeneration
Correction
Push correct valve settings in Master
Settings
Check the P11 connection and trigger a
manual regeneration.
Verify correct valve type is chosen. Trigger a
manual regeneration.
Trigger a manual regeneration.
Trigger a manual regeneration.
Trigger a manual regeneration.
Reconnect communication cables and push
setting in Master Settings.
Push correct system settings in Master
Settings.
Contact your Pentair representative.
Trigger a manual regeneration
Fleck NXT2 Timer