TROUBLESHOOTING GUIDE FOR LOCKOUT CONDITIONS
If
the heat
pump
goes
into lockout
on
a
high or
low
pressure
switch,
the cause
of
the
lockout
can
be
narrowed down
by
knowing
the
operating mode
and
which
pressure
switch
the
unit
locked out
on.
The
following
table
will
help track down
the
problem
once
this
information
is
known.
Note:
A
lockout condition
is
a
result
of
the heat
pump shutting
itself
off
to protect
itself,
never
bypass the
lockout
circuit.
Serious damage can be caused
by the
system
operating
without
lockout protection.
X[I.
TROUBLESHOOTING GUIDE FOR UNIT OPERATION
Evaporator
(air
coil)
ices
over
in
High
Pressure
(Condenser,
Air Coil
Side)
-Loss/lack
of
airflow
-High
return air temperatures (above
85oF)
-Dirty
(fouled)
condenser
coil
-Overcharged
refri gerant
circuit
Heating
Low
Pressure
@vaporator, Earth Coupled Water
Coil
Side)
-Loss/lack
of
flow
through
earth
coupled
coil
-Low
fluid
temperature operation
in
the earth
loop
-Freezing
fluid
in
heat
exchanger (lack
of
antifreeze)
-Undercharged/overcharged refrigerant
circuit
-Expansion valve/sensing
bulb malfunction
High
Pressure
(Condenser,
Earth Coupled Water
Coil
Side)
-Loss/lack
of
water
flow
in
earth
loop
-High
fluid
temperarure
operation
in
the earth
loop
-Dirry
(fouled)
condenser
coil
-Overchargq4
refri gerant
circuit
Cooling
Low
Pressure
(Anti-Short Cycle)
(Evaporator,
Air
Coil
Side)
-Loss/lack
of
airflow
-Low
air temperature (below
55T)
-Freezing condensation on air
coil
-Undercharged/overcharged refrigerant
circuit
-Expansior! valve/sensing
bulb malfunction
Blown
Fuse/Tripped
Circuit
Breaker
Replace fuse or
reset
circuit breaker"
(Check
for
correct
size
fuse or
circuit
breaker.)
Blown
Fuse
on
Controller
Replace
fuse
on
controller.
(Check
for
correct
size
fuse.)
Broken or Loose Wires
Replace or tighten the wires
Voltage
Supply
Low
If
voltage is
below minimum
voltage on
data
plate, contact local power
company.
Supply
below
196
volts
will
hamper compressor
startup.
Low Voltage
Circuit
Check transformer
and fuse
for
burnout or voltage
less
than
1
8
volts.
Thermostat
Set
thermostat on
"Cool"
and
lowest temperature setting,
wait for
timeout period
and
unit
should
run.
Set
thermostat on
"Heat"
and
highest temperature setting,
wait
for
timeout
period
and
unit
should
run.
If
unit
does
not run
in
both
cases,
the
thermostat could
be
wired
incorrectly
or
be
faulty.
To prove
faulty
or
miswired
thermostat, disconnect thermostat wires
at
the
unit
and
jumper
befween
"R",
"Y"
and
"G"
terminals
and
unit
should
run.
Replace
thermostat
with
correct
heat
pump
themostat
only. A
substitute may
not work properly.
Entire
unit
does
not run
Interruptible
Power
Check
supply voltage.
Dirty
Filter
Check
filter.
Clean or replace
if
found dirty.
Thermostat
Improperly
Set
Is
it
below
room temperature?
Clleck
the thermostat
setting.
Defective Thermostat
Check therrLostat
operation.
Replace
if
found defective.
lncorrect
Wiring
Check
for
broken, loose, or incorrect wires.
Unir
will
not
operate
on
"heating"
Blower Motor Defective
Check
blower
motor
in
one
of
the
other switch
positions.
ff
it
does
not
operate the
compressor
will
go
off
on
higlr
head.
Dirty
Air
Filter
Check
filter.
Clean or replace
iffound
dirty
Airflow
Lack of
adequate
airflow
or improper
distribution of
air.
Check
the
motor
sizing.
Check
the
filter,
it
should
be
inspected every month
and changed
if dirty.
Check
for
closed
registers.
Remove or
qdd resistance
accordingly.
speed and
duct
Low
Air
Temperature
Room temperatures
below
65oF
may ice over the evaporator
mode
13
1[[llg*
LOC{OUTCS}TSIIION
POSSIBI,{CAUSA
PB3BX,*Bi{
?OSSIBLACAUST
.CffiCKS
AND CORASCTIONS