Econar GeoSource Vara GV Series Installation And Operating Instructions Manual page 16

Vertical and horizontal forced air
Table of Contents

Advertisement

Thermostat
Wiring
Blown
Fuse
The
unit
could
be
off
on
the
high
or low-pressure cutout
control.
Check water
GPM,
CFM
and
filter,
ambient temperature
and
loss
of refrigerant.
If
the
unit
still
fails
to run,
arr
if
defective.
controls
check
for
High
or
Low
Pressure
Controls
If
voltage is
below minimum
voltage specified on
the data
plate, contact
local power
Check
terminal.
at
for
Voltage
Supply
Low
Check
transfofiner
and
fuse
for burn
out or voltage
less
that
18
volts. With
a
voltmeter,
check signal
from
thermostat
at
Y
to
X,
Ml
on
controller
to
X,
check
for
24
volts
across the
compressor
contactor.
Replace component that
does
not
energize.
Low Voltage
Circuit
Compressor Overload Open
ln
all
cases
an
"internal"
compressor overload is
used. If
the
compressor motor is too
the overload
will
not
reset
until
the
cqmpfgllgllqqlq
down.
hot,
lnternal winding
grounded to the compressor shell. Replace
the compressor,
burnout, replace
inline
filter
drier.
If
compressor
Compressor
Motor
Grounded
Check
continuity of
the compressor
windings with
an
ohmmeter.
If
the
windings
are open,
replace the compressor.
Compressor
Windings
Open
Seized
Compressor
Try
an
auxiliary
capacitor
in
parallel
with
the run capacitor
momentarily.
If
the
compressor
still
does
not start, repiace
it.
Blower motor
runs but
compressor
does
not,
or
compressor
short cycles
Improperly
located thermostat
(e.g. near
kitchen,
inaccurately
sensing the
comfort level in
living
areas).
Thermostat
Wirine
and
Controls
Loose
wiring
connections, or
control
contactor defective,
Compressor overload
works
on
high
temperature.
A
compressor
running
hot may
be
due to
lack
of refrigerant
charge
or
faulty
high-pressure
lockout.
Unit
short
cycles
Compressor Overload Engaging
Reversing
Valve
does
not Shift
Defective
solenoid valve
will
not
energize.
Replace solenoid
coil.
Unit
does
not
cool
(Heats
Only)
Reversing
Valve
does
not Shift,
the
Valve
is Stuck
The solenoid valve
is
de-energized due to
miswiring
at
the
unit
or thermostat-correct
wiring.
Replace
if
valve is
tight
or frozen
and
will
not
move.
Switch from
heating to
cooling
a
few
times to loosen valve.
Water
Lack of sufficient
pressure,
temperature or
quantity of
water
Unit
Undersized
Air
lraks
in
Ductwork
Check
for
leaks
in ductwork
or
introduction of
ambient air through doors/windows
Thermostat
Improperly
located thermostat (e.g.
near
kitchen,
not
sensing the
comfort
tevel
in
living
areas). Check anticipator setting.
Airflow
Lack of
adequate
airflow
or improper
distribution of
air.
Check the
motor
speed and
duct
sizing.
Check the
filter,
it
should
be
inspected every month
and
cleaned
if dirty.
Remove or
add resistance
accordingly.
Refrigerant Charge
Low
on
refrigerant charge causing
inefficient operation. Adjust only
after checking
CFM
and
GPM.
Reversing
Valve
reversing valve creating
bypass
of
refrigerant
from
discharge to suction
side
of
compressor. When
it
is
necessary to
replace
the
reversing valve, wrap
it
with
a
wet
cloth
and
direct
the heat
away.
Excessive
heat can damage
the valve.
Defective
Insufficient
cooling or
heating
Desuperheater
The
crcurt
should
disconnected
be
desuperheater
(inJine
fuse)
extreme
weather
cold
during
allow
to
fu11
to
load
house.
Unit
not
kvel
Level vertical
units.
Water drips
from unit
Condensate
Drain Line Kinked
or Plugged
Clean
condensate
Make
drain.
sure
external
drain
condensate
installed
ls
with
adequate
drop
and
Compressor
Make
sure
the compressor is not
in direct
contact
with
the base
or
sides
of
the
cabinet.
or
creates noise.
Blower
and
BIower Motor
Blower
wheel
hitting
the
casing, adjust
for
clearance
and
alignment.
Bent
blower,
check
and
Loose
blower
wheel
on
check
and
if
Contactors
A
or
m
nolse
the
"clattering"
contactor
be
could
to
due
"humming"
control
than
less
voltage
8
I
Check
volts.
low
for
low
transformer
or
voltage,
supply
tralsformer
outPut,
tap setting.
the
If
contactor contacts
are
corroded
OI
or
coil
IS
or
Rattles
and
Vibrations
loose
for
internal
OI
screws, panels,
could
be
the
Copper
components.
piping
hitting
metal
surfaces.
Water
and
Airborne
Noises
Noisy
0peration
Cavitating
Pumps
Purge
air
from
closed
loop
system.
Check
and
Check
for
loose or broken wires at
or contactor
fuse or
reset
circuit
breaker,
for
correct
size
fuse or
circuit
breaker
Recalculate
heat
gains or
losses
for
space
to
be
conditioned.
If
excessive,
rectify by
adding
etc.
Undersized
ductwork
will
cause
high
airflow
velocities
and
noisy
operation.
Excessive
water through the water
coil
will
cause
a
squealing
sound.
Check the water
flow
t4
flow for
but
the
noise.
,
ensuring
C{IEICKS
AND
CSRR*CTIONS
PROBLTM
POSSIBLECAUS$

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents