N Troubleshooting Guide For Unit Operations - Econar GeoSource Ultra GW Series Installation And Operating Instructions Manual

Hydronic
Table of Contents

Advertisement

XV.
TROUBLESHOOTING GUIDE FOR UNIT OPERATION
Blown
Fuse/Tripped
Circuit
Breaker
Replace fuse or reset
circuit
breaker. (Check
for
correct size fuse
or
circuit
breaker.)
Blown
Fuse
on
Controller
Replace fuse on
controller.
(Check
for
correct
size
fuse.)
Broken or
Loose Wires
Replace
or
tighten the wires.
Voltage
Supply
Low
If
voltage is
below minimum
voltage on
data
plate, contact
1oca1
power company.
Low Voltage
Circuit
Check
24-volt
transformer
for
burnout,
blown
fuse
or
voltage
less
than
I
8
volts
Remote
Hydronic Control or
RoomThermostat
Set
system
to
"Coo1"
and
lowest temperature setting,
unit
should
run.
Set
system
to
"Heat"
and
highest temperature setting,
unit
should run.
If
unit
does
not run
in
either
case, the
hydronic control
(or room thermostat) could be
faulty or
incorrectJy
wired.
To
prove faulty
or
miswired,
disconnect ttrermostat wires
at
the
unit
and
jumper
between
'R',
.Y'
and
"G" terminals,
and
unit
should run.
Only
replace
with
correct replacement.
A
substitute may
not work properly.
Entire unit
does
not
run.
Intemrptible
Power
Check
incoming
supply voltage.
Water
Lack of sufflcient
pressure,
flow,
temperature and/or
quantity of
water.
Unit
Undersized
Recalculate heat gains or
losses
for
space
to be conditioned.
lf
excessive,
rectify
by
adding
insulation,
shading,
etc.
Loss of
Conditioned
Air
by
Leaks Check
for
leak
in ductwork
or
introduction of
ambient air tbrough doors
and
windows.
Improperly
located thermostat
(e.g. near
kitchen
sensing inaccurately the
comfort
level in
living
areas).
Check
anticipator
settinq (Should
be
1.0
or
1.2).
Thermostat
Airflow
(Across fan
coil)
Lack of
adequate
airflow or improper distribution of air.
Check the
motor
speed
and duct
sizing.
Check the
filter, it
should
be
inspected every
month
and
changed
if
difi.
Remove
or
add
resistance
accordingly.
Refrigerant Charge
Low
on
refrigerant
charge causing
inefficient
operation.
Adjust only after
checking
CFM, GPM
and
inlet/outlet
temperatures.
Compressor
Check
for
defective compressor.
If
discharge
pressure
is
too
low
and suction
pressure
too high,
compressor
is
not
pumping properly.
Replace compressor.
Reversing
Valve
Defective
reversing valve creating bypass
of refrigerant from
discharge
to
suction
side
of
compressor. When
it
is
necessary
to replace the reversing valve, wrap
it
with
a
wet
cloth
and
direct
the
heat away. Excessive heat
can damage
the valve.
Insufftcient cooling or
heating
Desuperheater
The
desuperheater
circuit
(in-line
fuse) should
be
disconnected
during cold
weather
to allow
fuIl
heating load to house.
Remote
Hydronic Control or
Room Thermostat
Check setting
and
wiring. If
thermostat
has an
anticipator,
set
it
at
1.0
or
1
.2.
Wirine
Check
for
loose or
broken
wires
at
compressor, capacitor, or contactor,
Blown
Fuse
Replace fuse or
reset
circuit breaker.
(Check
for
correct
size
fuse
or
circuit
breaker.)
High
Pressure
or
Low
Pressure
Switch
or Discharge
Refrigerant
Temperature
Switch
The
unit
could be
off
on
high
pressure, low-pressure
or
discharge
refrigerant
temperature cutout. Check water
GPM
and
temperatures, ambient temperature
and
loss
of refrigerant.
If unit still
fails
to run,
individually
check
for faulty
switches
or
wiring.
Replace
if
defective.
Defective
Capacitor
Check capacitor,
if
defective remove, replace,
and
rewire correctly
Voltage
Supply
Low
If
voltage is
below minimum
voltage specified on the
data
p1ate,
contact
local
power company. Check voltage
at
compressor
for
possible
open
terminal.
Low
Voltage
Circuit
Check
24-volt
transformer
for burn
out
or
voltage
less
that
18
volts.
With
a
voltmeter,
check signal
fiom
thermostat
at
Y
to
X,
Ml
on
controller
to
X,
capacitor voltage drop. Replace component that
does
not
energize.
Compressor Overload Open
In
all
cases
an
"intemal"
compressor overload is
used.
If
the compressor
motor
is
too hot, the overload
will
not
reset
until
the compressor cools down.
If
the
compressor is
cool
and
the overload
does
not
reset,
there may be
a
defective
or
open overload. Replace the compressor.
Compressor
Motor
Shorted
to
Ground
Internal winding
grounded to
the
compressor shell. Replace the compressor.
If
compressor burnout replace
the
liquid
line filter/drier.
Compressor
Windings
Open
Check
continuity of
the compressor
windings
with
an
ohmmeter.
If
the
windings
are
open, replace
the
compressor.
Hydronic
pump runs
but
compressor
does
not, or
compressor
short cycles.
Seized
Compressor
Try
an
auxiliary
capacitor
in parallel
with
the
run capacitor
momentarily.
If
the
compressor
still
does
not
start,
replace
it.
1
T9
Pnf)Br,{M. ,
.
Pf)SSIBL:Efi{$f :,
';

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents