Condensate Drain; Earth Loop Water Piping - Econar GeoSource Vara GV Series Installation And Operating Instructions Manual

Vertical and horizontal forced air
Table of Contents

Advertisement

IIL
CONDENSATE
DRAIN
Condensate
traps
are
built into
every GeoSource
Vara
vertical unit,
so an
external trap should not
be
installed.
Vertical
units must
be
level
to
insure
proper
condensate
drainage. Horizontal
units require
an
external
condensate
trap
in
order to drain
water
from
the heat
pump.
Horizontal
units must
also be
mounted level
in
order
for
the condensate
to drain.
On
horizontal
units,
the condensate
line
as
it
leaves the
U
bend
of
the condensate
trap
must be at least
3"
below
the
base
of
the heat
pump.
This requires
the
U bend to
be
6"
below
the
unit
to give
the
upward
portion of
the
U bend
a
3"
lift.
The
condensate
trap should
be
vented after
the
U
bend.
The
condensate
line
should
be
pitched
away
from
the
unit
a
minimum
of
1/8"
per
foot.
If
the
unit
produces
an
odor
in
the
cooling mode,
the condensate
ffap or
line
may
be
plugged, or
ttre
unit
may
not be
pitched correctly.
Bleach may
be
poured down
the condensate
drain
in
the
heat
pump to
kill
any
bacterial
growth in
the condensate
line.
Vented
condensate
traps
aro
necessary to
break
the
negative
pressure
in
the air chamber
and
allow
the
condensate to
flow.
Construct
condensate traps
to
the
following
diagram.
Air
vo
3/4"Minim
diMcta
Hat
pmp bse
6"
Drop
To druifl
wi*r
1/8"
prfoot
-i.i-,-
pitr,h
@
3" Rise
Figure
1
-
Condensate
Drain
-
Horizontal Units Only
TO/IROM
CLOSED
LOOP
IV.
EARTH LOOP WATER
PIPING
Since
water is the
source
of
energy
in
the
wintertime
and
the
energy siak
in
the
summertime, good water supply is
possibly
the
most important requirement
of
a
geothermal
heat
pump
sy3tem
installation.
There
are
two
common
types
of
water supplies, closed
loop
systems and
open
loop
systems.
A.
Closed
Loop Applications
A
closed
loop
system
recirculates
the same
water/antifreeze solution through
a
closed
system
of
underground high-density polyethylene
pipe.
As
the
solution
passes
through
the
pipe,
it
collects
heat
(in
the
heating mode) that
is
being transferred
from
the
relatively
warm
srrrounding soil
through
the
pipe
and
into
the
relatively cold solution.
The solution is circulated to
the
heat
pump,
which pulls
heat
out
of
the solution,
and
then
back through the ground to extract more
heat
from
the
earth.
The GeoSource
Vara
is
designed
to operate
on
either
vertical or horizontal
closed
loop applications. Vertical
loops
are
typically
installed
with
a
well
drilling rig
up
to
200 feet
deep
or
more. Horizontal
systems are
typically
installed
with
excavating or trenching equipment
approximately six to eight feet
deep,
depending on
geographic
location
and
length
ofpipe
used.
Earth loops
must be sized
properly for
each
particular
geographic
area,
soil type,
and
individual
capacity requirements.
\
f
- -ll
___J
Figure
2
-
Closed
Loop
Water Plumbing
4
PmpPAK
ll
il
il
Preroey'
Tqrahre
en)Pdk
IN
OUT
I

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents