Unit Sizing; Electrical Service - Econar GeoSource Vara GV Series Installation And Operating Instructions Manual

Vertical and horizontal forced air
Table of Contents

Advertisement

c.
Miratic Acid
Cleaning
(Difficult
Scaling
and
Particle Buildup
Problems)
l.
Consult installer
due
to
dangerous nature
ofacids.
2.
Iron
out solutions
and
de-scaling products
are also
useful.
VI.
UNIT SIZING
Selecting
the
unit
capacity
of
a
geothermal
heat
pump
requires
two
things:
A)
Earth
Loop Configuration
and
Design Water
Temperatures.
B)
Building
Heat Loss/Heat Gain.
A.
Loop Configuration
and Design
Water Temperatures
Loop
configurations include
the open and closed
loop
varieties.
Heat pump capacity
and
flow
rate
requirements
vary depending on loop
configuration
(see
Table
3).
1.
Closed Loop Systems
Closed
loop
systems
use a
heat exchanger
of
high density
polyethylene pipe buried underground
to
supply
a
tempered
water solution back to
the heat
pump.
Closed
loops
operate at
higher
flow
rates than
open loops
since
the
entering water temperature
(EWT)
is
lower.
The
loop
EWT
supplied to
the heat
pump
has
a
great effect
on the
capacity
of
the
unit in
the
heating
mode.
Earth loops in
cold climates
are
normally
sized
to supply
a
wintertime
EWT
to
the heat
pump
from
32oF
down to
25oF,
which
minimizes
the
installation
cost
of
the
earth loop
and
still
maintains proper
system
operation.
The
unit GPM
requirements
and pressure drops
for
loop pump sizing
is
available
in
Table
2.
When selecting
the heat
pump,
choose
a
unit
that
will
supply
the necessary
heating or
cooling
capacity
at the
minimum
and
maximum
earth
loop temperature
conditions
respectively.
Example;
if
a
residential
system
requires 44,000
Btu/hr
to
heat
a
house on an earth
loop
system
(designed
for
32oF
minimum wintertime EWT),
and
34,000
Btu/hr
to
cool
the house
on
an earth
loop
(designed for
77nF
summertime
EWT),
a
Gx52x-x-Vxxx
GeoSource
Vara
heat
pump
is
required.
2. Open Loop Systems
On
an
open
loop
system the
design water temperature
will
be the
well
water temperature
in
your geographic region.
Many
cold climates
are
in
the
50oF
range
for well
water
temperature.
Flow
rate
requirements
(in GPM)
and
unit
water-side
pressure
drops (in PSI)
at
50"F
EWT
are
available
in
Table
3. If
your well
water
temperatures
are
lower
than 50oF,
for
instance
Canadian
well
water
can be
as
low
as
43T,
the
flow
rate must
be increased
to avoid
leaving water
temperatures
below
the
freezing
point.
If
well
water
temperatures are above
50"F,
as
in
some
southem
states
where
well
water
temperatures are above
70"F,
the
flow
rates
may
need to be increased
to dump
heat
more
efficiently in
the
cooling
mode.
Varying well
water temperatures
will
have
little
effect
on
unit
capacity
in
the
cooling
mode
(since the
well
is
connected to
the heat
pump
condenser),
but
can have
large effects on
the
capacity
in
the
heating mode
(since
the
well
is
connected
to
the
evaporator).
If
well
water
temperatures are
to
exceed 70t'F,
special considerations,
such
as
closed
loop
systems,
should
be addressed.
B.
Building
Heat Loss/fleat Gain
The
space
load
must be
estimated accurately
for
any
successful
HVAC installation.
There
are
many
guides
or
computer programs available
for
load estimation
including
the
ECONAR
GeoSource
Heat Pump
Handbook, Manual
J, and
others.
After
the heat loss/heat
gain is completed
and
loop
EWT
are established, the heat
pump
can
now be
selected
using
the
specifications
data.
Choose the
capacity
of
the heat
pump
based on
both
heating
and
cooling
load.
VII.
ELECTRICAL SERVICE
The main
electrical
service
must be
protected by
a
fuse
or
circuit
breaker,
and be capable
ofproviding
the amperes
required by
the
unit
at
nameplate
voltage.
All
wiring
shall
comply with
the
national electrical
code
and,/or
any
local
codes
that may
apply.
Access
to
the
line voltage
contactor
is
gained through
the
knockouts provided
on
either
side
ofthe
heat
pump next to
the
front
corner.
Route
EMT or flexible
conduit
with
appropriate
3-
conductor
wire
to
the
contactor.
9WARNING
-
The
unit
must
be
properly erounded!9
VCAUUON:
Three-phase units
ruI
be
wired
properly
to insure proper compressor
rotation. Improper
phasing may result
in
compressor damage.
An
electronic
phase sequence
indicator must
be used
to check supply-
wiring
phase.
Also,
the
"Wild"
leg
of
the
three-phase
power
must be connected
to the middle leg
on the
contactor.
When supplying power to external water pumps
with
the
heat
pump's power supply,
use
only
impedance
protected
motors. ECONAR
PumpPAKsrM
can be
wired
directly
to
the
contactor
in
the
electrical
box.
The relay
will
energize
the
PumpPAKrM
with
a
call for
heating or
cooling.
The
use
of
impedance
protected
pumps
eliminates
the need
for
additional fusing on
the
PumpPAKrM.
8
)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents