Service - Econar GeoSource Vara GV Series Installation And Operating Instructions Manual

Vertical and horizontal forced air
Table of Contents

Advertisement

AII
construction dust
has
been cleaned
up
and
all
sheet-rocking is
completed.
Construction
dust,
especially sheet-rock
dust, can
plug
the
air
coil
and
block
airflow.
Make
sure the
filter
is
clean
before
starting
the
unit.
Low
voltage
wiring of
the
thermostat
and any
additional
control wiring
is
complete.
Set
thermostat
to
the
"OFF"
position.
All
high
voltage
wiring
is correct
including
fuses,
breakers, and
wire
sizes.
The
heat
pump is located
in
a
warm
area
(above
45"F).
Starting the
system
with low
ambient
temperature conditions is more
dfficult;
do
not leave
until
the
space
is
brought
up
to
operating
temperatures.
You
may now apply power to
*te
unit.
A
4 minute
35
second
delay
on
power
up
is programmed
into
the heat
pump before
the
compressor
will
operate. During
this
time you
can
verify
airflow
with
the
following
procedure:
-
Place the
thermostat
in
the
"FAN
ON"
position.
The
blower
should
start
in
low
speed. Check
airflow
at
the
registers to make
sure
that they
are
open
and
that
air
is
being distributed throughout
the
house.
When
airflow
has
been checked,
move
the
thermostat to the
"FAN AIJTO" position.
The
blower
should
stop.
The
following
steps
will
assure
that
your
system
is
heating
and
cooling
properly. After
the
initial
power up
period is completed,
the
red
indicator fight
on the
internal
conffoller
will
shut
off.
The
heat
pump is now ready
for
operation.
-
With
the
thermostat
in
the
"HEAT"
mode, turn
the
thermostat up to
its
highest temperature
setting.
The
blower
should
start,
with
the
compressor starting
a
few
seconds
later.
The thermostat may
cause
its
own
compressor delay
at
this time but
the
compressor
will
start
after
all
delays.
-
After
running
the
unit for
5
minutes, check
the
airside
return
and
supply temperatures.
An
air temperature
rise
of
20oF
to
30oF
is
normal
in
the
heating
mode,
but variations
in
water temperature
and
water
flow
rate
cafl
cause
variations outside
the
normal
range.
-
Turn
the
thermostat to
the'OFF"
mode.
The
compressor
will
shut
down
in
a
few
seconds,
with
the
blower
stopping shortly after.
-
Next,
set
the
thermostat to
"COOL"
and
turn down to
its lowest
setting.
The
blower
will
start
immediately,
and the
compressor
will
start after
all
anti-short cycle
periods.
The anti-short cycle period
is
indicated
by
the
red
light
(labeled
ASC)
on
the
controller.
-
After
the
unit
has
run
in cooling for
5
minutes, check
the
airside return
and
supply temperatures.
An air
temperature drop
of
15oF
to 20"F is normal
in
the
cooling
mode
but
airflow
and
humidity
can
effect
temperature drop.
-
Set the
thermostat
for
normal operation.
-
Instruct
the
owner on
correctoperation
ofthe
thermostat
and heat
pump.
The
heat
pump is equipped
with
both
high
and
low
pressure
switches that
shut the
unit
off
if
the
refrigerant
pressure exceeds
400 psi or
goes
below
25
psi.
Ifthe
system exceeds
400 psi,
the
high-pressure switch
will trip
and
lock
the
unit
off
until
power
has
been
disconnected
at
the
circuit
breaker
for
approximately
one
minute.
System
pressures
below
25
psi
in
heating
will
trip
the
low
pressure
switch
and
lock
the
unit
out
until
the
power
supply
has
been
de-energized
for
one
minute.
On
a
well
water system,
the freeze
protection
switch
(fi
eld installed
part number 75-1028)
will
activate
the
lockout
at 35
psi
in
the
heating
mode
to protect
the
water
coil
against freeze
rupture. After
resetting
a
lockout
(by disconnecting
power to
the
unit) verify
that both water
flow
and
airflow
are at the
recommended levels before energizing
the
compressor.
DO
NOT
reset
a
well
water
system
without
verifying
water
flow.
DO
NOT
reset the system
more
than
one
time.
VRepeated resetting
of
the
lockout
can
cause serious damage
ifthe
reason
for lockout
is not
corrected.
I
-
Iflockout
occurs more than
once
contact
your
ECONAR
dealer
immediatelv.
I
X.
SERVICE
Regular
service
to
a
GeoSource
Vara
heat
pump
is
very
limited.
The biggest factor is cleaning the air
filter.
Other factors could include water
coil
maintenance
on
an
open
loop
system
(this maintenance is
discussed
in
section
V).
Setting
up
regular
service
checkups
with your
ECONAR
dealer
could
be
considered.
Any major
problems
with
the heat
pump
system
operation
will
be
indicated on
the
thermostat
lockout light.
A.
Filter
The GeoSource
Vara
heat
pump requires
an
electrostatic
air
filter
(ECONAR
part number 70-1066
for
GY
/
GH/
3
6 I
52,
7
0-
1067
f
or
GH/
59
/
67,
7
0
-
107
7
for
GY159167).
This
filter
can
be cleaned and reused
after
it
becomes
dfuty. This
fi1ter should
normally
be cleaned
once
a
month during normal usage.
During
extreme
usage
or
if
system
performance
has
decreased, the
filter
should
be cleaned
more often.
A
dfuty
filter
will
increase static pressure
to
the system.
This
increase
in
static pressure
will
cause
the variabte
speed
blower
to
increase
its
speed
in
order to maintain
airflow levels. This
increase
in
speed
will
consume
more
power
than
normal, reducing
the
efficiency of
the system.
In
extreme
cases,
the
blower
will
not
be able
produce
the
correct amount
of
airflow.
In
the
heating
mode, reduced
airflow
may
increase the
cost
of
operation
and,
in
extreme
cases,
cause system
lockout
due
to high
refrigerant
pressures.
In
the
cooling
mode,
reduced
airflow
may
reduce
cooling
capacity
and,
in
extreme
cases,
ice
the
aircoil
over causing
system
shutdown
due
to
low
refrigerant
pressures.
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents