Econar GeoSource Vara GV Series Installation And Operating Instructions Manual page 7

Vertical and horizontal forced air
Table of Contents

Advertisement

tContact
your
local installer
or
ECONAR's
Customer
Support
for loop
sizing requirements
in your
area.
Since
normal
wintertime
operating entering water
temperatures
(EW-f)
b
the heat
pump
are
from
25oF
to
32T,
the
solution
in
the earth
loop must
include
antifreeze. GTF
and
propylene
glycol
are
conlmon
antifreeze
solutions. GTF
is
methanol-based antifreeze,
which
should
be
mixed
50Vo
with
water to achieve freeze
protection
of
10oF. Propylene
glycol
antifreeze
solution
should
be
mixed
25Va
with
water to obtain a
15T
freeze
protection. DO
NOT
mix
more
that257o
propylene
glycol
with
water
in
an
attempt to achieve
a
lower
than
15oF
freeze protection,
since
more concentrated mixtures
ofpropylene glycol
become
too viscous
at
low
temperatures and cannot be
pumped through
the earth
loop.
Insufficient
amounts
of
antifreeze may result
in
a
freeze
rupture
of
the
unit,
and can
cause
unit
shutdown
problems during
cold
weather operation (when
the heat
pump
experiences the
longest run
time)
due
to loop
temperatures
falling
below the
freeze
protection
of
the
antifreeze.
Flow
rate
requirements
for
closed loops
are
higher than
open
loop
systems because
water temperatures supplied to
the heat
pump
are
generally
lower
(see
Table
3).
From
2.5
to
3.0
gallons per minute
(GPM)
per
ton
are
required
for
proper operation
of
the heat
pump
and
the earth
coupled
heat exchanger.
Table
3
-
Side
Flow
Rates
Pressure/Temperalure
P/T)
ports should
be
installed
in
the
entering
and
leaving water lines
of
the heat
pump on
a
closed
loop
system
(see
Figure
2). A
thermometer
can be
inserted
into
the
P/T
ports to
check
entering
and
leaving
water temperatures.
A
pressure gauge can also be
inserted
into
these
P/T ports to determine
the pressure
differential
between
the
entering
and
leaving
water. This
pressure
differential
can then be
compared to the
specification
data on each
particular
heat
pump to
determine
the
flow
rate
of
the system.
A
PumpPAKrM that is
individually
sized
for
each
application
can
supply pumping requirements
for
the
earth
loop
fluid.
The PumpPAKrM
can also be used
to
purge
the
loop
system.
The
PumpPAKru
is
wired direcfly
to
the
contactor
and operates
whenever
the
compressor
runs
(see
Electrical
Diagram - Figure
4).
If
a
PumpPAKru
is
not
used,
a
separate
pump
can be used
which
is energized
with
a
pump relay (note: electrical
code
will
require
a
fused
discomect for
pumps other than
PumpPAKsrM).
Filling
and
purging
a
closed
loop
system are
very
important
steps
to
assure
proper
heat
pump operation.
Each loop
must be
purged
with
enough
water
flow
to
assure
a
two
feet per
second
flow
rate
in
each
circuit
on
the
loop.
This
normally
requires a
lVz
to
3
HP high
head
pump to circulate
fluid
through
the
loop to remove
all
the
air out
of
the
loop
and
into
a
purging
tank. Allow
the
pump to
run
10
to
15
minutes after
the
last air bubbles
havebeenremoved.
Enough
attifreeze mustbe
added
to
give a
10T
to
151F
freeze
protection to
the earth
loop
system.
This
amount should
be
calculated
and added
to
the
loop
after purging is
complete.
Aft.er antifreeze
has
been
installed
it
should
be measured
with
a
hydrometer,
refractometer or any other device to determine the actual
freeztng
point of
the
solution. Remember that
a
low
antifreeze
level
will
lock
the heat
pump out on
low
pressure
during wintertime
operation.
The purge pump
can be used
to pressurize
the system
to
an
initial
static
pressure
of
30-40
psi.
Make
sure the
system
is
at
this
pressure
after
the
loop pipe
has
had
enough
time
to
stretch. In
order
to
achieve the 30
to
40
psi
initial
pressure, the
loop may
need
to
be
pressurized to
60 to
65
psi.
This
static
pressure
will
fluctuate
from
heating to
cooling
season,
but
the pressure
should always
remain
above
zero
so
circulation
pumps
do not cavitate
and
air
cannot be
pulled into
the system.
SFor
information
regarding
earth
loop
installations contact
your
local
installer,
distributor
or
factory
representative.
B.
Open Loop
Applications
An
open
system gets
its
name
from
the open
discharge
of
water after
it
has
been used
by
the heat
pump.
A
well
must be
available that
can
supply
all of
the
water
requirements
(see
Table
3)
of
the heat
pump along
with
any
other water requirements
drawing
off
that
same
well.
The
well
must be capable
of
supplying
the heat
pump's
required
flow
rate
for
up to
24 hours
per day on
the
coldest
winter
day.
Figure 3
shows the necessary
components
for
water
piping of
an open
system. First,
a
bladder type
pressure
tank
with
a
"draw down" of
at
least
lYztines
the
well
pump capacity must
be
installed on
the
supply
side
of
the
heat
pump.
Shut
off
valves
and
boiler
drains
on the
entering
and
leaving water lines
are
necessary
for future
maintenance issues.
A
screen
strailer
is
placed
on the
supply
line with
a
mesh size
of
40 or 60
and
enough
surface area
to
allow for
particle
buildup
between
cleanings.
Pressure/Temperature (P/T) ports
are
placed
in
the
supply
and
discharge lines
so
that thermometers or
pressure
gauges can be
inserted
into
the
water
stream.
5
Closed
Loop
Opea.Loop
Flow
Model
SJlow
d**al)
dP
,(asi)
dP
{rs0
G(V,H)
36
8
5.5
4
1.3
G(Y,H)
52
11
5.2
6
1.6
G(V,H)
59
13
6.0
9
3.1
G(V,H)
67
t4
1.0
10
3.8

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents