Troubleshooting Guide For Unit Operation - Econar GeoSurce Vara 2 Plus GV Series Lnstallation And Operating Lnstructions

Vertical and horizontal forced air
Table of Contents

Advertisement

XIV.
TROUBLESHOOTING GUIDE FOR UNIT OPERATION
B
lown
Fuse/Tripped
Circuit
Breaker
Replace fuse or
reset
circuit breaker.
(Check
for
correct
size fuse
or
circuit
breaker.)
Blown
Fuse
on
Controller
Replace
fuse on
controller.
(Check
for
correct
size
fuse.)
Broken or Loose
Wires
Replace or tighten the wires.
Voltage
Supply
Low
If
voltage
is
below minimum
voltage
on data
plate, contact
local
power
company,
Supply
below
196
volts
will
hamper compressor
startup.
Low Voltage
Circuit
Check transformer
and
fuse
for
burnout or voltage
less
than
18
volts.
Thermostat
Set
thermostat on
"Cool"
and
lowest temperature setting,
wait for
timeout period
and
unit
should
run.
Set
thermostat on
"Heat"
and
highest temperature setting, wait
for
timeout period
and
unit
should
run. If
unit
does
not run
in
both
cases,
the
thermostat
could
be
wired
incorrecfly
or
be
faulty.
To prove
faulty
or
miswired
thermostat,
disconnect thermostat wires
at the
unit
and
jumper
between
and
"G"
terminals
and
unit
should
run.
Replace thermostat
with
correct
heat
pump thermostat
only. A
substitute may not
work
properly.
Entire
unit
does
not
run
Intemrptible
Power
Check
incoming
supply voltage.
Dkry
Filrer
Check
filter.
Clean or replace
if
found
dirty
Thermostat
Improperly
Set
Is
it
below room temperature? Check
the
thermostat setting
Defective Thermostat
Check thermostat
operation.
Replace
iffound
defective.
Incorrect
Wiring
Check
for
broken, loose, or incorrect wires.
Unit
will
not
operate
on
"heating"
Blower Motor
Defective
Check
blower
motor
ia
one
of
the
other switch
positions.
If it
does
not
operate the
compressor
will
go
offon
high
head.
Dirty Air Filter
Check
filter.
Clean or
replace
if
found
dirty
Airflow
Lack of
adequate
airflow
or improper
distribution of
air.
Check
the
motor
speed
and
duct
sizing.
Check
the
filter,
it
should
be inspected
every month
and changed
if dirty
Check
for
closed
registers.
Remove or
add resistance
accordingly.
Blower
Speed Set
too
Low
Verify
blower
speed
jumpers
are
in
factory
settings.
Low
Air
Temperature
Room
temperatures
below
65oF
may ice over
the
evaporator
Thermostat
Check setting,
calibration,
and
wiring,
Wirine
Check
for
loose
or broken wires
at
compressor, capacitor, or contactor
Blown
Fuse
Replace
fuse
or
reset
circuit breaker.
(Check
for
correct
size fuse
or
circuit
breaker.)
High
or
Low
Pressure
Controls The
unit
could
be
off
on the
high or low-pressure cutout
control.
Check water
GPM, air
CFM
and
fllter,
ambient temperature
and loss
of refrigerant.
If
the
unit still fails
to run,
check
for faulty
prglsure
conftols
individually.
Replace
if
defective.
Voltage
Supply
Low
If
voltage
is
below minimum
voltage specified
on the data
plate, contact local power
company.
Check voltage
at
compressor
for
possible
open
terminal.
Low Voltage
Circuit
Check transformer
and fuse
for
burn out or voltage
less
that
18
volts. With
a
voltmeter,
check signal
from
thermostat
at
Y1
to
X,
M1
on
controller
to
X,
check
for
24 volts
across the
compressor
contactor.
Replace component that
does
not
energize.
Compressor Overload Open
In all
cases
an
"internal"
compressor overload is
used.
If
the
compressor motor is too
hot,
the
overload
will
not
reset
until
the
compressor cools down.
Compressor
Motor
Grounded
Internal winding
grounded to
the
compressor shell. Replace
the
compressor.
If
compressor burnout, replace
inline
filter
drier.
Compressor
Windings
Open
Check
continuity of
the
compressor windings
with
an
ohmmeter.
If
the
windings
are
open, replace the compressor.
Blower
motor
runs
but
compressor
does
not,
or
compressor
short cycles
Seized
Compressor
Try
an
auxiliary
capacitor in
parallel with
the
run capacitor
momentarily.
If
the
compressor
still
does
not
start,
replace
it.
Thermostat
Improperly
located thermostat
(e.g. near
kitchen, inaccurately
sensing the
comfort level
in
livi4g
areas).
Wiring
and
Controls
Loose
wiring
connections.
or control
contactor defective.
Unit
short
cycles
Compressor Overload
Engaging
Compressor overload works
on
high
temperature.
A
compressor running hot
refrigeranl
charge
or
faulty
high-pressure lockout.
mav
be due
to lack
of
Evaporator
(air coil)
ices
over
in
cooling
mode
15
,ROBLEM
POSSISLE
CAUSE
C}IECKS AND CORRECTIONS

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents