Observe prior to installation
For each number of collectors, there is a specific allo-
cated number of rafter anchors or mounting brackets
(for use on sheet steel roofs).
The spacing between rafters and the potential snow
loads dictate how many rafters need to be used for the
installation.
The following tables specify which rafters the rafter
anchors or mounting brackets should be secured to.

Type SV (vertical collectors)

1 collector
2 rafters are required for all snow loads.
2 collectors
Rafter spacing in
Snow load in kN/m
mm
600
700
800
900
1000
3 collectors
Rafter spacing in
Snow load in kN/m
mm
600
700
800
900
1000
6
2
0.75
>
1, 4
1, 3
1, 3
2
0.75
>
1, 3, 5
Example:
2 collectors type SV
Rafter spacing a 600 mm
Snow load 0.75 N/m
Of the 4 rafters, the following are used:
Rafters 1 and 4
=
Fig. 1
Position of rafter anchors
A
Mounting rails
B
0.75/
1.25
1.25/
>
1, 3, 4
1, 2, 3
1, 2, 3
0.75/
1.25
1.25/
>
1, 2, 4, 5
1, 2, 4, 5
1, 2, 3, 4
1, 2, 3, 4
2
a
A
B
=
2.55
2.55/
>
1, 3, 4
1, 2, 3
1, 2, 3
2.55
2.55/
>
1, 3, 4, 6
4.80
4.80