4. General description
Placement and Installation
4.14. Condensate run off
concrete base
Special actions have to be set for the appearing condensate. As a result of a defrosting circle
up to 15 lt. condensate within 2 minutes can occur on every evaporator unit. It must be ensured,
that the condensate is discharged. The condensate outlet must be secured by the pre-mounted
heating cable. The heating cable extends approx. 1 m into the drain hose
To avoid overheating or a defect of the condensation run-off heating, following points must be
observed. The heating cable must not be laid in loops, and only as a single cable. The heating
cable must not touch itself (grinding - minimum distance 50 mm). Smallest bending radius 25 mm.
22
Well/pipe
condensation
run off
Installation instructions TERRA AL 60 Max
concrete base
min. 200 mm
300 mm
Canalisation
(C) IDM Energiesysteme GmbH
heating side connectio
electrical connections