Sub Menus - Siemens SITRANS F US SONOFLO SONO 3300 Handbook

Ultrasonic flowmeter sensor type and signal converter type
Hide thumbs Also See for SITRANS F US SONOFLO SONO 3300:
Table of Contents

Advertisement

® ® ® ® ®
SITRANS F US SONOFLO
User code setup

7.4 Sub menus

Flow direction
Volume flow
Sound velocity
7. Starting up
The user code can be changed in this menu.
The code is factory-set at 1000. If the user code is lost, the factory setting can be re-established as
follows: Switch off supply voltage, press the TOP-UP key
Release the key after ROM and RAM tests are completed. The user code is now reset to 1000.
If the signal converter is left in CONVERTER SETUP for more than 10 minutes, the converter
automatically reverts to OPERATOR MENU.
The figure on previous page gives a view of the menu build up. Below is a more detailed description
of the submenus. Use menu block diagram to step through to required sub-menu. (See also detailed
diagram blocks).
Information regarding the service menu is placed in the section "Trouble shooting".
The flow direction is defined for volume and mass flow simultaneously.
VOLUME
FLOW
VOLUME FLOW
UNIT: m
UNIT: m
UNIT: m
UNIT: l/s
UNIT: l/min
UNIT: l/h
UNIT: ml/s
UNIT: UGPS
UNIT: UGPM
UNIT: UGPH
UNIT: MUGPO
UNIT: Ml/d
Choose engineering unit and the maximum volume flow range.
For SONO 3000 not fitted with a SENSORPROM
It is done as follows:
a) Sensor ≤ DN 2000:
In the menu "MAX. RANGE" a value 10 x "VOL. FLOW MAX." should be entered.
b) Sensor > DN 2000:
In the menu "MAX. RANGE" a value 5 x "VOL. FLOW MAX." should be entered.
(Max. 540,000 m³/h).
The engineering units for the sound velocity are in meters per second. The measuring range is set
by entering the minimum and the maximum sound velocity.
Error relay and error indication are activated, if the sound speed is outside the limits stated.
SFIDK.PS.029.Q3.02
MAX RANGE
3
/s
3
/min
3
/h
®
unit the display indication must be formatted.
SOUND
VELOCITY
SOUND
SOUND
VELOCITY
VELOCITY
MIN.
MAX.
and switch on the supply voltage.
VOL. FLOW
MAX.
39

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents