7. Starting up
Select flow, direction and engineering units. By selecting bidirectional flow the net flow, i.e. the
difference between the positive and the negative flows, will be displayed.
Low flow cut-off can be set over a range from 0 - 9.9% of the measuring range.
In forced control it is possible to define the behavior of a current or frequency output in the event
of a fatal error. By selecting "off" the output remains on the latest valid reading.
MIN. forces the output to 0% in the event of an error and MAX. forces the outputs to 100%.
CURRENT
OUT
CURRENT OUT
OFF
VOLUME FLOW
MASS FLOW
SOUND VELOCITY
Bidirectionel
SFIDK.PS.029.Q3.02
CURRENT OUT
CURRENT OUT
BIDIRECTIONAL
4 - 20 mA
UNIDIRECTIONAL
0 - 20 mA
CURRENT OUT
TIME CON.
XX.XS
Unidirectionel
41