Friedrich ZONEAIRE SELECT PZE07K3SA Service & Parts Manual page 18

Ptac
Table of Contents

Advertisement

Electrical Data
MODEL
PZE / PZH07K
PZE / PZH09K
PZE / PZH12K
PZE / PZH15K
PZE / PZH09R
PZE / PZH12R
Electrical Wiring for 265 Volt
Models
Power Cord Installation
All.265V.PTAC/PTHP.units.come.with.a.factory.installed.non-LCDI.
power.cord.for.use.in.a.subbase..If.the.unit.is.to.be.hard-wired.refer.to.
the.instructions.below.
NOTE:.
It. is. recommended. that. the. PXSB. subbase. assembly,. the.
PXCJA.conduit.kit.(or.equivalent).be.installed.on.all.hardwire.
units...If.installing.a.
chassis. can. be. removed. from. the. sleeve. for. service. and.
maintenance.
Electrical Shock Hazard
Turn off electrical power before service
or installation.
ALL electrical connections and wiring
MUST be installed by a qualified
electrician and conform to the National
Code and all local codes which have
jurisdiction.
Failure to do so can result in property
damage, personal injury and/or death.
18
14
SPECIFICATIONS
HEATER kW
3.0
3.0
3.0
5.0
3.0
3.0
.mounted.unit,.make.sure.the.
WARNING
TABLE 2
Power Cord Kit
Voltage
STD
230/208
STD
230/208
STD
230/208
STD
230/208
STD
265
STD
265
To install the line voltage power leads and conduit
to chassis, follow the instructions below and refer
to Figures 25-27 on page 19. PXCJA Conduit Kit
is required with this setup.
Follow. the. removal. process. of. the. chassis's. junction. box. .
1.
(Figure.25,.step.2,.page.19).
. P repare.the.265V.(or.230V).power.cord.for.connection.to.the.chas-
2.
sis'.power.cord.connector.by.cutting.the.cord.to.the.appropriate.
length.(refer.to.Figure.26.and.follow.Figure.15)...Power.cord.harness.
selection.shown.on.Table.2.on.page.14.
Amperage
Receptacle
15
NEMA 6-20r
20
NEMA 6-20r
20
NEMA 6-20r
30
NEMA 6-30r
20
NEMA 7-20r
20
NEMA 7-20r

Advertisement