Quick Links

PowPak
| Installation
®
CCO Module
Part of the Energi TriPak
Family
®
24 V~ 45 mA
RMJ-CCO1-24-B
NEC
24 V- 35 mA
URMJ-CCO1-24B
UL 2043 Plenum Rated
Important Notes:
Please read before installing.
• F or installation by a qualified electrician in accordance with all local and national
electrical codes.
• Note: Use copper conductors only.
• Check to see that the device type and rating is suitable for the application.
• DO NOT install if product has any visible damage.
• If moisture or condensation is evident, allow the product to dry completely before
installation.
• Operate between 32 °F (0 °C) and 131 °F (55 °C).
• 0% to 90% humidity, non-condensing.
• For indoor use only.
PowPak
®
CCO Module
Install in center of room to
maximize RF coverage.
Radio Powr Savr
TM
Occupancy Sensor
30 ft (10 m)
Maximum
Pico
®
Wireless Transmitter
40 ft (12 m)
FCC Information:
This device complies with part 15 of the FCC Rules and Industry Canada licence-exempt RSS
standard(s). Operation is subject to the following two conditions:
(1) This device may not cause interference, and
(2) This device must accept any interference, including interference that may cause undesired
operation.
Modifications not expressly approved by Lutron Electronics Co., Inc. could void the user's
authority to operate this equipment.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference in a residential installation. This equipment generates,
uses and can radiate radio frequency energy and, if not installed and used in accordance with
the instructions, may cause harmful interference to radio communications. However, there is no
guarantee that interference will not occur in a particular installation. If this equipment does cause
harmful interference to radio or television reception, which can be determined by turning the
equipment off and on, the user is encouraged to try to correct the interference by one or more of
the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected.
Limited Warranty
(Valid only in U.S.A., Canada, Puerto Rico, and the Caribbean.)
Lutron will, at its option, repair or replace any unit that is defective in materials or manufacture
within one year after purchase. For warranty service, return unit to place of purchase or mail to
Lutron at 7200 Suter Rd., Coopersburg, PA 18036-1299, postage pre-paid.
This warranty is in lieu of all other express warranties, and the implied warranty of merchantability
is limited to one year from purchase. This warranty does not cover the cost of installation, removal
or reinstallation, or damage resulting from misuse, abuse, or damage from improper wiring or
installation. This warranty does not cover incidental or consequential damages.
LUTRON'S LIABILITY ON ANY CLAIM FOR DAMAGES ARISING OUT OF OR IN
CONNECTION WITH THE MANUFACTURE, SALE, INSTALLATION, DELIVERY, OR USE
OF THE UNIT SHALL NEVER EXCEED THE PURCHASE PRICE OF THE UNIT.
This warranty gives you specific legal rights, and you may have other rights which vary from
state to state. Some states do not allow the exclusion or limitation of incidental or consequential
damages, or limitation on how long an implied warranty may last, so the above limitations may
not apply to you. NEC is a registered trademark of National Fire Protection Association, Quincy,
Massachusetts. Lutron, Energi TriPak, Pico, PowPak and
are registered trademarks and
Radio Powr Savr is a trademark of Lutron Electronics Co., Inc.
©2012 Lutron Electronics Co., Inc.
Lutron Electronics Co., Inc. | 7200 Suter Road
Coopersburg, PA 18036-1299, U.S.A.
PowPak
| Instalación
®
Módulo CCO
Parte de la familia de productos Energi TriPak
®
24 V~ 45 mA
RMJ-CCO1-24-B
NEC
24 V- 35 mA
URMJ-CCO1-24B
Clasificado UL 2043 Plenum
Notas importantes:
Lea antes de la instalación.
• D ebe ser instalado por un electricista calificado en conformidad con los
códigos eléctricos locales y nacionales.
• Nota: Utilice solamente conductores de cobre.
• V erifique que el tipo y la clasificación del dispositivo sean adecuados para
la aplicación.
• NO realice la instalación si el producto presenta algún daño visible.
• Si hay señales de humedad o condensación, deje secar completamente el producto
antes de la instalación.
• Opere entre 0 °C (32 °F) y 55 °C (131 °F).
• 0% a 90% de humedad, sin condensación.
• Para uso en interiores únicamente.
Módulo
CCO
PowPak
®
Instale en el centro de la habitación
para aumentar la cobertura de RF.
Sensor de presencia
Radio Powr Savr
TM
10 m (30 pies)
Máximo
Transmisor inalámbrico
Pico
®
12 m (40 pies)
Información relacionada con la FCC:
Este dispositivo cumple con la Parte 15 de las normas de la FCC y las normas RSS para
productos exentos de licencia de la Industria de Canadá. La operación está sujeta a las
siguientes dos condiciones:
(1) Este dispositivo puede no causar interferencia, y
(2) Este dispositivo debe aceptar cualquier interferencia, incluso interferencias que puedan causar
problemas de funcionamiento no deseados.
Las modificaciones que no estén expresamente aprobadas por Lutron Electronics Co., Inc.
podrían anular la autorización del usuario para operar este equipo.
NOTA: Este equipo se ha sometido a pruebas y cumple con los límites correspondientes a
dispositivos digitales Clase B, conforme a la Parte 15 de las normas de la FCC. El objetivo
de estos límites es brindar una protección razonable contra la interferencia perjudicial en
instalaciones residenciales. Este equipo genera, utiliza y puede emitir energía de radiofrecuencia
y, si no se instala y utiliza conforme con las instrucciones, puede provocar interferencias
perjudiciales en las comunicaciones de radio. Sin embargo, no se garantiza la ausencia de
interferencias en cada instalación en particular. Si este equipo provoca interferencia perjudicial
para la recepción de ondas de radio y televisión, lo cual se puede determinar apagando y
encendiendo el equipo, se recomienda al usuario intentar corregir la interferencia mediante una o
más de las siguientes acciones:
• Reorientar o reubicar la antena receptora.
• Aumentar la separación entre el equipo y el receptor.
• Conectar el equipo a un tomacorriente que pertenezca a un circuito diferente de aquel al que
está conectado el receptor.
Garantía Limitada
(Válida solamente en E.U.A., Canadá, Puerto Rico y el Caribe).
Lutron, a su opción, reparará o sustituirá cualquier unidad que presente defectos en los
materiales o la mano de obra en el lapso de un año a partir de su compra. Para el servicio de
garantía, devuelva la unidad al lugar donde se efectuó la compra o envíela por correo a Lutron a
esta dirección: 7200 Suter Rd., Coopersburg, PA 18036-1299, con el franqueo prepagado.
Esta garantía sustituye todas las demás garantías expresas y la garantía implícita de
comerciabilidad está limitada a un año a partir de la compra. Esta garantía no cubre el costo
de instalación, remoción o reinstalación, ni los daños resultantes del mal uso, abuso o daños
provocados por cableado o instalación inadecuados. Esta garantía no cubre daños incidentales
ni consiguientes.
LA RESPONSABILIDAD DE LUTRON CON RESPECTO A CUALQUIER RECLAMACIÓN
POR DAÑOS QUE SURJAN DE LA FABRICACIÓN, VENTA, INSTALACIÓN, ENTREGA O
USO DE LA UNIDAD, O QUE ESTÉN RELACIONADOS CON ESTO, EN NINGÚN CASO
EXCEDERÁ EL PRECIO DE COMPRA DE LA UNIDAD.
Esta garantía le concede derechos legales específicos y usted puede obtener otros derechos
que varían de un estado a otro. Algunos estados no permiten la exclusión o limitación de daños
incidentales o consiguientes, ni la limitación del tiempo que pueda durar una garantía implícita,
de manera tal que las limitaciones anteriores podrán no aplicarse en su caso. NEC es una marca
registrada de National Fire Protection Association, Quincy, Massachusetts. Lutron, Energi TriPak,
Pico, PowPak y
son marcas registradas y, Radio Powr Savr es una marca registrada de
Lutron Electronics Co., Inc. © 2012 Lutron Electronics Co., Inc.
Lutron Electronics Co., Inc. | 7200 Suter Road
Coopersburg, PA 18036-1299, E.U.A.
Lutron Electronics Co., Inc. | 7200 Suter Road
Coopersburg, PA 18036-1299, E.U.A.
Required Components
For each system ensure you have:
At least one PowPak
CCO Module.
041-374
®
Rev. B
06/2012
CLASS 2
®
CCO
CCO Toggle
Status
LED
Advanced
Operations
Contact
Closure
Output
(CCO)
(Class 2)
PowPak
CCO Module
®
Start Here
1
Install PowPak
CCO Module
®
When installing a PowPak
Module, use the supplied mounting
screws and wire the module as shown.
All Wireless
Suggested Installation Location:
Transmitters
must be
Install in center of room.
installed within
This ensures proper RF coverage of area.
30 ft (10 m) of
the PowPak
®
CCO Module.
Note: PowPak
CCO Module may also be
®
mounted on or inside a junction box.
If installing unit inside a junction box please
see Application Note #423.
For more information:
www.lutron.com/powpakcco
2
Associate Wireless Transmitters to PowPak
Before beginning this step, make sure that there are no other PowPak
from other systems can be incorrectly associated to this system.
A
Permanently install
3
Wireless Transmitters
Link
Test
Note: Please consult individual
component installation guides
for information.
Componentes requeridos
Para cada sistema, asegúrese de contar con:
Al menos un módulo PowPak
CCO.
®
041-374
Rev. B
06/2012
Conmutador
CLASS 2
LED
®
CCO
indicador
de estado
CCO
Operaciones
Salida de
avanzadas
contacto
seco (CCO)
(Clase 2)
Módulo PowPak
CCO
®
Comience por aquí
1
Instale el módulo PowPak
Para instalar el módulo PowPak
de contacto seco (CCO), use los tornillos
de montaje proporcionados y conecte el
módulo como se muestra en la figura.
Todos los
Ubicación sugerida para la instalación:
transmisores
inalámbricos
Instálelo en el centro de la habitación.
deben
instalarse
Esto garantiza una cobertura adecuada de RF del área.
dentro de 10 m
(30 pies) de un
Nota: El módulo PowPak
CCO también
módulo CCO
®
puede montarse sobre o dentro de una caja
PowPak
.
®
de conexiones.
Si instalará la unidad dentro de una caja de
conexiones, consulte la nota de aplicación #423.
Para obtener más información, visite:
www.lutron.com/powpakcco
2
Asocie los transmisores inalámbricos al módulo PowPak
Antes de comenzar con este paso, asegúrese de que no se estén instalando otros módulos PowPak
transmisores inalámbricos de otros sistemas a este sistema.
A
Instale transmisores
3
inalámbricos de
forma permanente
Link
Test
Nota: Consulte las guías de
instalación de los componentes
para obtener más información.
Need Help? www.lutron.com or call the Lutron Technical Support Center, 24/7 at 1.800.523.9466
At least one Wireless Transmitter
+
Radio Powr Savr
TM
Occupancy Sensor
(6 maximum)
Supply Voltage
CCO
®
24 V~ / 24 V-
Wire nut
(2 Supplied)
COM
(Common)
NC
NO
(Normally Closed)
(Normally Open)
CCO Module
®
modules being set up within the same building. It is possible that Wireless Transmitters
®
Hold the CCO Toggle
Hold the indicated button on a Wireless Transmitter for
B
button on the PowPak
6 seconds to associate the device.*
®
CCO Module for 6 seconds
Repeat for any additional Wireless Transmitters.
to enter association mode.
Test
* If no g button, hold "Lights Off" button.
Note: The CCO will open and close
Hold the CCO Toggle button on the PowPak
C
once after each step to confirm
successful completion.
CCO Module for 6 seconds to save association(s).
Note: Only complete step 4 if using a Daylight Sensor with the CCO Module
4
Daylight Sensor setup
to control a device that is switching a lighting source.
Calibration
A
Turn lights in room on using the
CCO Toggle button on the PowPak
®
CCO Module or an associated Pico
.
®
Press & hold "Cal." on the associated
B
Daylight Sensor for 6 seconds.
Exit room for 5 minutes to allow
C
calibration to be completed.
Note: When calibration has completed, all lights
will flash and the system will begin daylighting.
¿Necesita ayuda? Visite www.lutron.com o llame al Soporte técnico de Lutron al +1.888.235.2910 24 / 7
Al menos un transmisor inalámbrico.
+
Sensor de presencia
Radio Powr Savr
TM
(Máximo de 6)
CCO
Voltaje de
®
alimentación
con salida
®
24 V~ / 24 V-
Tuerca
para cable
(2 proporcionadas)
COM
(Común)
NO
NC
(Normalmente
(Normalmente Abierta)
Cerrada)
Mantenga presionado el
Mantenga presionado el botón indicado del transmisor inalámbrico
B
botón conmutador CCO
durante 6 segundos para asociar el dispositivo.*
del módulo PowPak
Repita esta acción para asociar otros transmisores inalámbricos.
®
CCO durante 6 segundos
para ingresar al modo de
asociación.
Test
Nota: La CCO se abrirá y cerrará
* Si no hay un botón g, mantenga presionado el botón "Lights Off" (Apagar Luces).
una vez después de cada paso
para confirmar que el proceso se
Mantenga presionado el botón conmutador CCO del módulo
C
completó con éxito.
PowPak
CCO durante 6 segundos para guardar las asociaciones.
®
Configuración del
Nota: Sólo siga este paso si utiliza un sensor fotoeléctrico con el
4
sensor fotoeléctrico
Calibrado
A
Encienda las luces de la habitación
utilizando el botón de conmutación
CCO del módulo PowPak
CCO
®
o un Pico
asociado.
®
B
Presione y mantenga presionado "Cal."
en el sensor fotoeléctrico asociado
durante 6 segundos.
C
Salga de la habitación durante 5 minutos
para permitir que se complete el calibrado.
Nota: Cuando se complete el calibrado las luces
parpadearán activando el sensor fotoeléctrico.
Link
Cal.
Test
Pico
Radio Powr Savr
®
TM
Wireless Transmitter
Daylight Sensor
(9 maximum)
(1 maximum)
Note: CCO Module supply wires can be
connected in any polarity.
Mounting screw
(2 Supplied)
To CCO-controlled device.
Note: When wiring CCO output,
use 20 to 16 AWG (0.5 to 1.5 mm
)
2
solid or stranded wire.
Link
®
Tuning (Optional)
A
If it is desired to have multiple zones of
lights turn on at different daylight levels
Link
Cal.
Test
(using multiple CCO Modules with one
Daylight Sensor) follow the Tuning
procedure described in the Daylight
Sensor
installation instructions.
(LRF2-DCRB)
Use the CCO Toggle button in place of
the Dimmer/Switch tap button referenced
in the document.
Link
Cal.
Test
Transmisor inalámbrico
Sensor fotoeléctricos
Pico
Radio Powr Savr
®
TM
(Máximo de 9)
(Máximo de 1)
Nota: Los cables de alimentación
del módulo CCO pueden conectarse
en cualquier polaridad.
Tornillo de montaje
(2 proporcionados)
Para el dispositivo
controlado por CCO.
Nota: Al realizar el cableado de
una salida CCO, use un cable
sólido o trenzado de 0,5 a 1,5 mm
(20 a 16 AWG).
CCO
®
en el mismo edificio. Es posible que se asocien por error
®
Link
Test
módulo CCO para controlar un dispositivo que funciona
como interruptor de una fuente de luz.
Ajuste (Opcional)
Si desea tener múltiples zonas
A
iluminadas con diferentes niveles de
Link
Cal.
luz del día (usando múltiples módulos
Test
CCO con un sólo sensor fotoeléctrico),
siga los pasos del procedimiento de
ajuste descritos en las instrucciones
para la instalación del sensor
fotoeléctrico
.
(LRF2-DCRB)
Utilice el botón conmutador CCO en
lugar del botón atenuador/interruptor
al que hace referencia el texto.
CCO Information
• This product features a single contact closure output with both
normally open (NO) and normally closed (NC) dry contacts.
• The CCO incorporates maintained output behavior only.
• The CCO is rated to switch resistive loads at
Switching
Resistive
voltages up to 24 V only. To properly control
Voltage
Load
R
inductive load types such as relays, solenoids,
0-24 V-
1.0 A
or motors, refer to Application Note #434.
0-24 V~
0.5 A
Transmitting Device Transmitted Command
CCO Default Action
Pico
Wireless
On
NO = Close, NC = Open
®
Transmitter
Off
NO = Open, NC = Close
Raise
No Action
Lower
No Action
Preset
NO = Close, NC = Open
Radio Powr Savr
Occupied
NO = Close, NC = Open
TM
Occupancy Sensor
Unoccupied
NO = Open, NC = Close
Radio Powr Savr
Occupied
No Action
TM
Vacancy Sensor
Unoccupied
NO = Open, NC = Close
Radio Powr Savr
Ambient light below target
NO = Close, NC = Open
TM
Daylight Sensor
level
Ambient light above target
NO = Open, NC = Close
level
Unaffected Mode
Unaffected mode allows a system with an Occupancy Sensor
associated to multiple CCO Modules to be set up such that only
selected loads turn on automatically. Other loads will require a
manual turn-on with a Pico
Wireless Transmitter. All loads will turn
®
off automatically when the room is vacated.
On a CCO Module, press and hold both the CCO
A
Toggle and Advanced Operations ("ADV") buttons for
6 seconds until the LED begins flashing quickly.
On the associated Occupancy Sensor, press and hold
B
the "Test" button* for 6 seconds until the lens flashes.
Unaffected mode will be exited automatically. This
C
CCO Module will now be unaffected by occupancy
commands. Repeat procedure for any additional
devices.
* If no "Test" button, hold "Lights On" button.
Reset Factory Defaults
Note: In some instances it may be necessary to reset the
PowPak
CCO Module back to factory default settings.
®
Triple-tap the Advanced Operations ("ADV") button
A
on the CCO Module and hold until the LED begins to
flash slowly.
Within 3 seconds of flashing, release and triple-tap the
B
button again and the LED will flash rapidly indicating
that the unit has been reset to factory defaults.
Note: Any associations or programming previously set up with the
Cal.
unit will be lost and will need to be re-programmed.
Test
Troubleshooting
www.lutron.com
CCO-
• Ensure power to the PowPak
CCO Module is
®
controlled
properly applied.
device does
• Ensure the CCO-controlled device has been
not respond
properly wired to the PowPak
CCO Module.
®
to Wireless
• Ensure Wireless Transmitter is properly
Transmitter(s)
associated to PowPak
CCO Module.
®
• Ensure Wireless Transmitter's battery is installed
correctly.
Wireless
• The maximum number of Wireless Transmitters
Transmitter(s)
have been associated to the PowPak
CCO
®
cannot be
Module. To remove a previously set up Wireless
associated to
Transmitter, tap the button used for association
PowPak
on the Wireless Transmitter three times, on the
®
CCO Module
third tap hold for three seconds and then tap
three more times.
Información de CCO
• Este producto presenta una salida de contacto seco con contactos
secos normalmente abiertos (NO) y normalmente cerrados (NC).
• La CCO sólo incorpora un comportamiento de salida permanente.
• La CCO está clasificada para conmutar cargas de resistencia
a voltajes superiores a 24 V
Voltaje de
Carga de
únicamente. Para controlar cargas
conmutación
resistencia
inductivas tales como relés,
R
solenoides o motores refierase a la
0-24 V-
1,0 A
nota de aplicación #434.
0-24 V~
0,5 A
Dispositivo Transmisor Mando Transmitido Acción predeterminado
de la CCO
Transmisor
Encendido
NO = Cerrada, NC = Abierta
inalámbrico Pico
®
Apagado
NO = Abierta, NC = Cerrada
Subir
Ninguna acción
Bajar
Ninguna acción
Predeterminado
NO = Cerrada, NC = Abierta
Sensor de presencia
Ocupado
NO = Cerrada, NC = Abierta
Radio Powr Savr
TM
Desocupado
NO = Abierta, NC = Cerrada
Sensor de vacancia
Ocupado
Ninguna acción
Radio Powr Savr
TM
Desocupado
NO = Abierta, NC = Cerrada
Sensor fotoeléctrico
Luz ambiental por
NO = Cerrada, NC = Abierta
Radio Powr Savr
debajo del objetivo
TM
Luz ambiental por
NO = Abierta, NC = Cerrada
encima del objetivo
Modo desafectado
El modo desafectado permite configurar el sistema con un sensor de
presencia asociado a varios módulos de CCO para que únicamente
las cargas seleccionadas se enciendan automáticamente. Las
otras cargas se deberán encender manualmente con un transmisor
inalámbrico Pico
. Todas las cargas se apagarán automáticamente
®
cuando la habitación quede desocupada.
En el módulo CCO, presione y mantenga presionados
A
el botón conmutador del CCO y el botón operaciones
avanzadas ("ADV") durante 6 segundos hasta que el
indicador LED comience a parpadear rápidamente.
En el sensor de presencia asociado, presione y
B
mantenga presionado el botón "Test" (Prueba)* durante
6 segundos hasta que la lente parpadee.
Saldrá del modo desafectado automáticamente. Este
2
C
módulo CCO ahora está desafectado en relación a los
comandos de presencia. Repita el procedimiento para
otros dispositivos adicionales.
* Si no hay botón "Test" (Prueba), presione el botón "Lights On"
(Encender Luces).
Restablezca los valores de
fabricación predeterminados
Nota: En algunas ocasiones puede ser necesario restablecer la
configuración predeterminada del módulo PowPak
CCO.
®
Presione tres veces el botón de operaciones avanzadas
A
("ADV") del módulo CCO y mantenga presionado
hasta que el indicador LED comience a parpadear
lentamente.
Antes de tres segundos de parpadeo, libere el botón y
Cal.
B
presiónelo tres veces nuevamente hasta que el indicador
LED parpadee con rapidez, lo que indica que se han
restablecido los valores predeterminados de la unidad.
Nota: Todas las asociaciones o programas configurados
anteriormente en la unidad se perderán y deberán programarse
nuevamente.
Solución de problemas
www.lutron.com
El dispositivo
• Asegúrese de que el módulo PowPak
CCO esté
®
controlado
correctamente conectado.
por CCO no
• Asegúrese de que el dispositivo controlado por
responde
CCO esté correctamente conectado al módulo
a los
PowPak
CCO.
®
transmisores
• Asegúrese de que el transmisor inalámbrico esté
inalámbricos.
asociado correctamente al módulo PowPak
CCO.
®
• Asegúrese de que la batería del transmisor
inalámbrico esté instalada correctamente.
Los
• Se ha asociado el número máximo de
transmisores
transmisores inalámbricos al módulo PowPak
®
inalámbricos
CCO. Para quitar un transmisor inalámbrico
no pueden
configurado anteriormente, presione el botón
asociarse
utilizado para asociar transmisores inalámbricos
al módulo
tres veces, la tercera vez mantenga presionado
PowPak
durante tres segundos y luego presione el botón
®
CCO.
tres veces más.

Advertisement

loading

Summary of Contents for Lutron Electronics TriPak Series

  • Page 1 PowPak 6 seconds to associate the device.* Note: In some instances it may be necessary to reset the Modifications not expressly approved by Lutron Electronics Co., Inc. could void the user’s ® PowPak CCO Module back to factory default settings.
  • Page 2 Repita o procedimento para qualquer transmissor sem fio adicional. um funcionamento indesejável. Nota: Em alguns casos pode ser necessário restaurar os padrões PowPak CCO por As modificações não aprovadas expressamente pela Lutron Electronics Co., Inc. podem invalidar de fábrica do módulo PowPak CCO. ® ®...

This manual is also suitable for:

Powpak rmj-cco1-24-bPowpak urmj-cco1-24b