Changing Interface Parameters - Beko BEKOMAT 33iU Original Installation And Operation Manual

Table of Contents

Advertisement

BEKOMAT
®
33iU / 33iU CO

3.4.3.3 Changing interface parameters

INFORMATION
i
This process is used to change interface parameters required for communication.
1. Write the value 0xAC1D (decimal: 44061) to Holding Register 0x1392 (Decimal: 5010).
2. Write the parameter to the Holding Register 0x07D0 (decimal: 2000).
Description / explanation
HighByte:
See the following table
LowByte:
Modbus Client address 1 ... 246
Example value:
0x070A (decimal: 1802)
For interface parameters see table Index 0x07 (decimal: 7)
Client Address 0x0A (decimal: 10)
3. To save the settings, write the value 0xBA5E (decimal: 47710) to Holding Register 0x139C (Decimal: 5020).
4. Switch the product off and switch it back on again. 
0 The changes will go into effect approx. 10 seconds after the restart.
Parameter - HighByte
Baud
Selection
rate [Bd]
0x00
4800
0x01
4800
0x02
4800
0x03
9600
0x04
9600
0x05
9600
0x06
19200
0x07
19200
0x08
19200
0x09
38400
0x0A
38400
0x0B
38400
20 | 68
BEKO TECHNOLOGIES configuration tools!
BEKO TECHNOLOGIES recommends using the Software Integrator to change the interface
parameters. The software can be downloaded from the BEKO TECHNOLOGIES homepage
(see "1.1 Contact" on page 5).
To connect to a PC, BEKO TECHNOLOGIES recommends using the Integrator Hardware Kit
(for ordering information, see chapter "11.2 Accessories" on page 55).
Parity
Stop Bit
No
2
Even
1
Odd
1
No
2
Even
1
Odd
1
No
2
Even
1
Odd
1
No
2
Even
1
Odd
1
Original installation and operation manual
Parameter - HighByte
Baud
Selection
rate [Bd]
0x0C
57600
0x0D
57600
0x0E
57600
0x0F
76800
0x10
76800
0x11
76800
0x12
115200
0x13
115200
0x14
115200
Parity
Stop Bit
No
2
Even
1
Odd
1
No
2
Even
1
Odd
1
No
2
Even
1
Odd
1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bekomat 33iu coBm33iuBm33iu co

Table of Contents