3

MAINTENANCE

3.1

Spare parts manual

3.2

Post start-up maintenance

After the compressor has run for the initial 100 operating hours:
i.
ii.
iii.
iv.
v.
vi.
vii.
3.3

First maintenance

Renewal of oil discharge filter
Inspection of suction gas filter(s)
Inspection of oil suction filter
Inspection leakage shaft seal
8
P-NL-094_imm_VHS_English_13
26.07.2021
Hint!
A complete spare parts overview is available as a separate manual.
Download the parts list manual via GEA website or consult your sales
representative.
Drain the oil and refill the compressor with the correct amount of fresh oil.
Replace the running oil discharge filter element with the "permanent" filter
element in accordance with the filter replacement instructions.
Inspect suction gas filter (refer to the Compressor Service Instruction
Manual).
Exchange or clean oil suction filter element.
Check the compressor shaft seal for leakage. If excessive (more than 1 cc/hr)
contact your compressor supplier
Retighten the coupling mounting bolts with the torque settings as given by the
coupling manufacturer.
Verify and if necessary, correct the torque settings of all foundation bolts as
given in Compressor Service Instruction Manual.
Hint!
For complete conditional service schedules and service intervals,
refer to Guideline for Conditional maintenance.
After the refrigerating plant has been modified, inspect/clean the
suction gas filter(s) and the oil filters.
After the refrigerating plant has been modified, the oil must be
changed.
Maintenance
(strainer)
8
Oil analysis
Consult your oil supplier.
Number of operating hours
100
X
X
refer to Guideline for Conditional
X
X
X
MAINTENANCE
Spare parts manual
> 100
Maintenance
41