Oil Quantities Vhs - GEA Grasso VHS Series Installation And Maintenance Instructions Manual

Reciprocating compressors for industrial refrigeration
Table of Contents

Advertisement

Procedure:
i.
ii.
iii.
iv.

1.4.3.1 Oil quantities VHS

Number of cylinders
P-NL-094_imm_VHS_English_13
26.07.2021
Warning!
Oil charging via the suction line of the compressor is not allowed.
Used or filtered oil should NEVER BE added to a compressor under
any circumstance.
Use only new oil as selected from the Grasso oil table. (Refer
Chapter 4, Page 50)
STATUS: System is dried and still evacuated.
Charge the oil separator (if present) initially with oil .
Close suction and discharge stop valves of compressor and oil return line of
oil separator (if present).
Charge the compressor crankcase with oil via the oil charge valve.
Warning!
Pre-lubrication just before the first start is obligatory.
Hint!
Filling of the afore mentioned components is also possible by means
of a separate oil filling pump via the oil charge valves mounted onto
the oil pump housing.
Shaft seal housing incl.
V 700HS
V 1100HS
V 1400HS
V 1800HS
INSTALLATION AND PREPARATION FOR USE
internal circuit of
crankshaft
0.7
PREPARATIONS FOR USE
1.5
0.9
Crankcase
(max/min)
22.4 / 16.5
31.9 / 23.5
45.6/ 33.6
55.1/40.6
25

Advertisement

Table of Contents
loading

Table of Contents