P14 Group Serial Communication - Kruger Ecowatt Drive K120 Series Operation Manual

Table of Contents

Advertisement

Ecowatt
®
Drive K120 series
Function
Name
code
High-frequ
ency
P13.12
compensat
ion
coefficient
Short-circu
P13.13
it braking
current
Hold time
of
P13.14
short-circu
it braking
before start
Hold time
of
P13.15
short-circu
it braking
for stop

P14 group Serial communication

Function
Name
code
Local
communic
P14.00
ation
address
Communic
P14.01
ation baud
rate
The function code is valid when the motor
speed exceeds the rated speed. If motor
oscillation occurred, adjust the function code
properly.
Setting range: 0.0–100.0%
When the VFD starts in direct start mode
(P01.00=0), set P13.14 to a non-zero value to
enter short-circuit braking.
During stop, if the running frequency of VFD
is lower than the starting frequency of brake
for stop, set P13.15 to a non-zero value to enter
short-circuit braking for stop, and then carry
out DC braking in the time set by P01.12.
(Refer to the descriptions for P01.09–P01.12.)
Setting range of P13.13: 0.0–150.0% (VFD)
Setting range of P13.14: 0.00–50.00s
Setting range of P13.15: 0.00–50.00s
Setting range: 1–247
When
the
master
communication address to 0 indicating a
broadcast address in a frame, all the salves
on the Modbus bus receive the frame but do
not respond to it.
Local communication address is unique in
the communication network, which is the
basis
for
point-to-point
between the upper computer and the VFD.
Note: The communication address of a slave
cannot be set to 0.
The function code is used to set the data
transmission
speed
computer and the VFD.
0: 1200BPS
Description
Description
writes
communication
between
-106-
Function parameter list
Default
0.0%
0.0%
0.00s
0.00s
Default
the
slave
the
upper
4
Modify
Modify
1