P11 Group Protection Parameters - Kruger Ecowatt Drive K120 Series Operation Manual

Table of Contents

Advertisement

Ecowatt
®
Drive K120 series
Function
Name
code
Multi-step
P10.37
time unit
selection

P11 group Protection parameters

Function
Name
code
Phase loss
P11.00
protection
Frequency
drop at
P11.01
transient
power-off
Frequency
drop ratio
P11.02
at
transient
power-off
0: Second; the running time of each step is
counted in seconds;
1: Minute; the running time of each step is
counted in minutes.
0x00–0x11
Ones place:
0: Disable input phase loss protection
1: Enable input phase loss protection
Tens place:
0: Disable output phase loss protection
1: Enable output phase loss protection
0: Enable
1: Disable
Setting range: 0.00Hz/s–P00.03 (max. output
frequency)
After the grid powers off, the bus voltage
drops to the frequency drop point at transient
power-off, the VFD begins to decrease the
running frequency based on P11.02, to make
the
motor
generate
returning power can maintain the bus
voltage to ensure a rated running of the VFD
until the VFD is powered on again.
Voltage degree
Frequency drop
point at transient
power-off
Note:
 Adjust the parameter properly to avoid
the stopping caused by VFD protection
during the switching of the grid.
 Disable the input phase loss protection
before enabling this function.
Description
Description
power
again.
220V
380V
260V
460V
-100-
Function parameter list
Default
0
Default
11
0
The
10.00Hz/s
660V
800V
Modify
Modify