P03 Group Vector Control - Kruger Ecowatt Drive K120 Series Operation Manual

Table of Contents

Advertisement

Ecowatt
®
Drive K120 series

P03 group Vector control

Function
Name
code
Speed loop
P03.00
proportion
al gain 1
Speed loop
P03.01
integral
time 1
Low-point
frequency
P03.02
for
switching
Speed loop
P03.03
proportion
al gain 2
Speed loop
P03.04
integral
time 2
High-point
frequency
P03.05
for
switching
The parameters P03.00–P03.05 are applicable
only to vector control mode. Below the
switching
frequency
speed-loop PI parameters are: P03.00 and
P03.01. Above the switching frequency 2
(P03.05), the speed-loop PI parameters are:
P03.03
and
P03.04.
obtained according to the linear change of
two groups of parameters. See the following
figure:
PI parameter
P03.00, P03.01
P03.02
The
speed
loop
characteristics of vector control can be
adjusted
by
coefficient
and
regulator. Increasing proportional gain or
reducing
integral
dynamic response of speed loop; however, if
the proportional gain is too large or integral
time is too small, system oscillation and
overshoot may occur; if proportional gain is
too small, stable oscillation or speed offset
may occur.
PI parameters have a close relationship with
the
inertia
of
parameters depending on different loads to
meet various demands.
Setting range of P03.00: 0–200.0
Setting range of P03.01: 0.000–10.000s
Setting range of P03.02: 0.00Hz –P03.05
Setting range of P03.03: 0–200.0
Setting range of P03.04: 0.000–10.000s
Setting range of P03.05: P03.02–P00.03 (Max.
output frequency)
Description
1
(P03.02),
PI
parameters
P03.03, P03.04
Output frequency f
P03.05
dynamic
setting
the
proportional
integral
time
time
can
the
system.
-51-
Function parameter list
Default
20.0
the
0.200s
are
5.00Hz
20.0
0.200s
response
of
speed
accelerate
10.00Hz
Adjust
PI
Modify