P13 Group Sm Control - Kruger Ecowatt Drive K120 Series Operation Manual

Table of Contents

Advertisement

Ecowatt
®
Drive K120 series
Function
Name
code
Speed
deviation
P11.15
detection
time
Automatic
frequency
reduction
P11.16
during
voltage
drop

P13 group SM control

Function
Name
code
Pull-in
current
P13.00
reduction
coefficient
Initial pole
P13.01
detection
method
Pull-in
P13.02
current 1
The function code is used to set the speed
deviation detection time.
Actual detection
value
Set detection
value
t1<t2, so the VFD continues running
t2=P11.15
Setting range of P11.15: 0.0–10.0s
0: Disable
1: Enable. When the grid voltage drops to the
rated voltage, the VFD ensures the rated
output
torque
reduction.
0.0–100.0%
0: Do not detect
1: High-frequency superposition (reserved)
2: Pulse superposition
Pull-in current is the pole positioning
current. Pull-in current 1 is valid within the
lower limit of pull-in current switchover
frequency threshold. If you need to increase
the starting torque, increase the value of the
function code properly.
Setting range: 0.0%–100.0% (of the motor
rated current)
Description
Speed
t1
t2
Running
Fault output
by
automatic
Description
-104-
Function parameter list
Default
0.5s
Time t
dEu
frequency
Default
80.0%
20.0%
Modify
0
Modify
0