P17 Group Status Viewing - Kruger Ecowatt Drive K120 Series Operation Manual

Table of Contents

Advertisement

Ecowatt
®
Drive K120 series
Function
Name
code
Transmissi
P14.05
on error
processing
Communic
ation
P14.06
processing
action

P17 group Status viewing

Function
Name
code
Set
P17.00
frequency
Output
P17.01
frequency
Ramp
P17.02
reference
frequency
Output
P17.03
voltage
communication
communication interval exceeds the value.
In general, the function code is set to 0.0.
When
continuous
required, you can set the function code to
monitor communication status.
0: Report an alarm and coast to stop
1: Keep running without reporting an alarm
2: Stop in enabled stop mode without
reporting an alarm (applicable only to
communication mode)
3: Stop in enabled stop mode without
reporting an alarm (applicable to any mode)
0x00–0x11
Ones place:
0: Respond to write operations. The VFD
responds to read and write commands of the
upper computer.
1: Not respond to write operations. The VFD
responds only to the read commands of the
upper computer. This mode can improve the
communication efficiency.
Tens place:
0: Communication encryption is invalid.
1: Communication encryption is valid.
Displays current set frequency of the VFD.
Range:0.00Hz–P00.03
Displays current output frequency of the VFD.
Range: 0.00Hz–P00.03
Displays current ramp reference frequency of
the VFD.
Range: 0.00Hz–P00.03
Displays current output voltage of the VFD.
Range: 0–1200V
Description
fault"
(CE)
communication
Description
-108-
Function parameter list
Default
if
the
is
0
0x00
Default
0.00Hz
0.00Hz
0.00Hz
0V
Modify
Modify