Quick Start Guide
5.2.2
Configure using a handheld communicator
The options available in the Guided Setup wizard include all items required
for basic operation.
Procedure
1. Turn on the handheld communicator and connect to the device.
2. Select Configure → Guided Setup.
3. Select Basic Setup and follow the on-screen instructions.
5.2.3
Configure using the LOI
The Guided Setup wizard is not available on the LOI (Local Operator
Interface).
22
Rosemount 2140 and 2140:SIS Level Detectors
July 2021