July 2021
Switching HART revision using a handheld communicator
To switch the HART revision mode from DD-based handheld communicator:
Procedure
1. From the Home screen, select Configure.
2. Select Manual Setup → HART → Communication Settings →
Change HART Revision.
3. Change the HART revision.
Switching HART revision using the LOI
To switch the HART revision mode using the LOI (Local Operator Interface):
Procedure
1. Press any LOI configuration button to activate the menu.
2. Scroll down ( ) and then select EXTENDED MENU ( ) .
3. Scroll down ( ) and then select HART REV ( ) .
4. To change HART revision, select HART REV 5 ( ), or scroll down ( )
and then select HART REV 7 ( ).
5. Exit the menu system by either waiting one minute for the EXIT
MENU? prompt, or scrolling down menus to find and select BACK TO
MENU and EXIT MENU.
5.2
Configure the level detector using guided setup
5.2.1
Configure using AMS Device Manager
The options available in the Guided Setup wizard include all items required
for basic operation.
Procedure
1. Start AMS Device Manager.
2. Select View → Device Connection View.
3. In the Device Connection View, double-click the HART modem icon.
4. Double-click the device icon.
5. Select Configure → Guided Setup.
6. Select Basic Setup and follow the on-screen instructions.