dehn DEHNrecord SD Manual page 68

Multifunctional measurement and analysis device for monitoring power quality
Table of Contents

Advertisement

12.
Technical data
Measurement power quality
Measurement method
Evaluation
Measurement
Nominal value voltage/frequency
Measurement power quality
Voltage magnitude
Frequency
Flicker
Dip, swell
Interruption
Unbalance
Harmonics, Interharmonics
Mains signalling voltage
Rapid voltage changes
EN 61000-4-30:2015, class A
EN 50160:2010 + Cor. 2010 + A1:2015 or individually parameterizable
3-phase (L1, L2, L3, N/PEN)
230 V
/ 50 Hz
eff
Measuring range
10 - 150 % of U
N
± 15 % of f
N
0.2 - 10 P
st
10 - 150 % of U
N
< 10 % of U
N
0.5 - 5 % of u
and u
2
0
Order 2. - 50.
0 - 15 % von U
N
± 1 % of U
to dip/swell
N
Page 68 from 69
Measurement accuracy/method
± 0.1 % of U
N
± 10 mHz
EN 61000-4-15
0.2 % of U
, ± 1 period
N
0.15 %
EN 61000-4-7 (class I)
EN 61000-4-30
0.2 % of U
N