Measured values – recording
Cyclic measurement
(SoL – sign-of-life-data)
Measured values are transmitted cyclically
to the cloud and are available there for
graphical display in the grid of observation
periods (1 week).
For evaluation and transmission, the
measured values are calculated to 5-minute
intervals (current, power, energy) or 10-mi-
nute intervals (PQ) UTC time-synchronously.
Event-based
An event is generated when a parameteri-
zed limit value is violated. The device trans-
fers the determined characteristic values
and detailed event data to the cloud.
This reduces the scope of measured values
obtained to the relevant data.
This can be done from all measurement
functions. In conjunction with the high-re-
solution temporal detailed data, this func-
tion provides a detailed fault record.
Events can also be assigned to different
output channels: LED, digital output, e-mail.
Events are categorized by basic device
functions (device, PQ, impulse current, ...)
and their sub-functions – e.g. for PQ:
voltage magnitude, frequency, unbalance
User-controlled
The user can start a fast data transfer by
pressing a button on the device or via the
cloud.
The 3-second average values are continu-
ously sent to the cloud over a period of 10
minutes.
This enables a detailed insight into the
current status quo.