Anti-Vibration Mounts; Rubber Anti-Vibration Mounts - Daikin UATYA-BFC2Y1 Instructions For Installation, Use And Maintenance Manual

Rooftop packaged unit
Table of Contents

Advertisement

6.2 Anti-vibration mounts

In order to reduce vibrations transmitted to the structure, it is advisable to install the unit on rubber or spring anti-
vibration mounts, supplied as an accessory and to be requested when placing the order.
The dimensional diagram with footprint shows the position and load of each anti-vibration mount.
The anti-vibration mounts must be fixed on before positioning the unit on the ground.
To install the anti-vibration mounts, see the instructions attached to the accessory.
When fixing the anti-vibration mounts, the unit should be lifted off the ground by no more than 200 mm
and no parts of the body should be placed under the unit.
6.2.1

Rubber anti-vibration mounts

The anti-vibration mount consists of an upper metal bell in which there is a screw for fixing it to the base of the unit.
The anti-vibration mount is fixed to the base through the two holes on the flange. The flange of the anti-vibration
mount bears a number (45,60,70 ShA) that identifies the hardness of the rubber support.
We reserve the right to make changes without any prior notice.
UATYA
4P645202-2
Fig. 23 Rubber/metal anti-vibration mounts
Translation from original instructions
Packaged Rooftop