Daikin UAT150C Technical Manual

Daikin UAT150C Technical Manual

Packaged air conditioner rooftop c series uat-c series

Advertisement

R22
TECHNICAL MANUAL
Packaged Air Conditioner
Rooftop C Series
UAT-C series
— Cooling only [50Hz] —

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the UAT150C and is the answer not in the manual?

Questions and answers

Summary of Contents for Daikin UAT150C

  • Page 1 TECHNICAL MANUAL Packaged Air Conditioner Rooftop C Series UAT-C series — Cooling only [50Hz] —...
  • Page 3: Table Of Contents

    UAT-C_(i) Table of Contents Table of Contents Nomenclature........................1 Features..........................2 Fan Performance Chart ......................6 Fan Performance Table ....................10 Engineering & Physical Data ................... 11 Performance Data ......................12 Outlines & Dimensions ....................16 Wiring Diagrams .......................18 Installation .........................26 Specifi cation Guide ......................28 Engineering & Physical Data (Arabic) ................29 Specifi...
  • Page 4: Nomenclature

    Nomenclature UAT-C_(i) Nomenclature UAT 300 C Product Type UAT: Rooftop Size Revision/Specification 150: 150,000 Btu/h 9: Mechanical Control 300: 300,000 Btu/h “ ”: PCB Control Product series C: C Series Power Supply Y1: 50Hz / 3Ph / 380-415V Product Specification Variation Product Origin G: Gold Fin (Outdoor Coil)
  • Page 5: Features

    UAT-C series is allows for ease of transportation and installation. developed with the target of high EER. Separate Service Panels Model UAT150C UAT180C The unit is designed with two separate service panels for easy electrical box servicing. Gross EER @ 35°C 11.5...
  • Page 6: All Standard Coils Are 3-4 Rows / 14-16 Fpi

    Features UAT-C_(i) Component Features Compressor Condenser Coil High effi ciency, low noise, and hermitically sealed Condenser coils are manufactured from seamless SCROLL compressors are used in the UAT-C series inner grooved copper tubes mechanically bonded to to give a better performance. aluminium fi...
  • Page 7 UAT-C_(i) Features Refrigerant Circuit Electrical Control Panel The UAT-C series is designed with the ability to The control panel is protected by a panel cover operate at partial load depending on the requirement to prevent nuisance changes by unauthorized of the application. personnel.
  • Page 8 Features UAT-C_(i) Microprocessor Based Control The control system consists of a microprocessor controller and a user interface remote controller. The controller offers the following features: • Built in anti recycle timer to prevent compressor short cycling • Sequential control of compressor, condenser motor and evaporator motor •...
  • Page 9: Fan Performance Chart

    UAT-C_(i) Fan Performance Chart Fan Performance Chart UAT150C 1400 3.0 kW 1300 1200 2.2 kW 1100 1000 1.5 kW Standard Point Internal Static Pressure 3600 4100 4600 5100 5600 1700 1900 2100 2300 2500 2642 Air Flow...
  • Page 10 Fan Performance Chart UAT-C_(i) UAT180C 3.7 kW 1400 3.0 kW 1300 1200 1100 2.2 kW Standard Point 1000 Internal Static Pressure 5200 5700 6200 6700 7200 7700 2454 2600 2800 3000 3200 3400 3630 Air Flow...
  • Page 11 UAT-C_(i) Fan Performance Chart UAT240C 5.5 kW 3.7 kW 3.0 kW Standard Point Internal Static Pressure 6500 7000 7500 8000 8500 9000 9500 4480 3270 3670 4070 3070 3470 3870 4270 Air Flow...
  • Page 12 Fan Performance Chart UAT-C_(i) UAT300C 5.5 kW 1200 1100 3.7 kW 1000 Standard 3.0 kW Internal Static Pressure 7000 7500 8000 8500 9000 9500 10000 10500 3300 4955 4100 4300 4900 3500 3700 3900 4500 4700 Air Flow...
  • Page 13: Fan Performance Table

    (Factory Setting) 1020 1120 1165 3600 Motor Output (kW) Air Flow = 4600 CFM 1020 1095 1150 1230 UAT150C 4600 ESP = 12.5/125 mmH O/Pa Motor Output (kW) Fan Speed = 905 1020 1090 1150 1230 5600 Motor Output (kW)
  • Page 14: Engineering & Physical Data

    Engineering & Physical Data UAT-C_(i) Engineering & Physical Data Engineering Data – R22 Model MODEL UAT150C UAT180C UAT240C UAT300C 150000 192300 255000 314300 Btu/h COOLING CAPACITY [1] 43.96 56.36 74.74 92.12 144200 185100 245000 300000 Btu/h COOLING CAPACITY [2] 42.26 54.25...
  • Page 15: Performance Data

    UAT-C_(i) Performance Data Performance Data Model: UAT150C Outdoor temperature EWB EDB 19.0°C 25.0°C 30.0°C 35.0°C 40.0°C 46.0°C 48.0°C 52.0°C (CFM) 21.0°C 43.44 30.23 10.25 42.07 29.57 10.96 40.60 28.86 11.77 39.03 28.11 12.71 37.11 26.73 13.76 34.81 25.07 15.02 34.37 24.75 15.43 32.84 23.65 16.27 24.0°C 43.61 36.01 10.26 42.23 35.26 10.97 40.77 34.47 11.79 39.22 33.63 12.72 37.29 31.98 13.77 34.98 30.00 15.04 34.53 29.61 15.44 32.99 28.29 16.29...
  • Page 16 Performance Data UAT-C_(i) Model: UAT180C Outdoor temperature EWB EDB 19.0°C 25.0°C 30.0°C 35.0°C 40.0°C 46.0°C 48.0°C 52.0°C (CFM) 21.0°C 55.69 38.76 13.27 53.93 37.91 14.18 52.05 37.00 15.24 50.04 36.04 16.45 47.82 34.44 17.95 45.15 32.51 19.75 44.19 31.82 20.42 42.41 30.54 21.63 24.0°C 55.91 46.17 13.29 54.15 45.21 14.20 52.27 44.19 15.26 50.28 43.12 16.47 48.04 41.20 17.97 45.36 38.90 19.78 44.39 38.07 20.45 42.61 36.54 21.65 16.0°C 26.7°C 56.12 53.14 13.30 54.41 52.15 14.22 52.58 51.08 15.28 50.71 49.76 16.50 48.46 47.55 18.01 45.75 44.89 19.81 44.78 43.94 20.49 42.98 42.17 21.69...
  • Page 17 UAT-C_(i) Performance Data Model: UAT240C Outdoor temperature EWB EDB 19.0°C 25.0°C 30.0°C 35.0°C 40.0°C 46.0°C 48.0°C 52.0°C (CFM) 21.0°C 73.86 53.48 18.04 71.52 52.30 19.28 69.03 51.06 20.72 66.36 49.73 22.36 63.40 47.51 24.69 59.85 44.85 27.48 57.25 42.90 28.39 54.88 41.13 30.25 24.0°C 74.14 63.71 18.06 71.81 62.38 19.30 69.32 60.98 20.74 66.67 59.50 22.38 63.70 56.84 24.72 60.13 53.66 27.51 57.52 51.33 28.42 55.14 49.20 30.28 16.0°C 26.7°C 74.42 73.33 18.08 72.15 71.96 19.33 69.73 69.73 20.77 67.25 67.25 22.43 64.25 64.25 24.76 60.65 60.65 27.57 58.02 58.02 28.47 55.62 55.62 30.34...
  • Page 18 Performance Data UAT-C_(i) Model: UAT300C Outdoor temperature EWB EDB 19.0°C 25.0°C 30.0°C 35.0°C 40.0°C 46.0°C 48.0°C 52.0°C (CFM) 21.0°C 91.03 61.64 22.25 88.15 60.28 23.78 85.08 58.84 25.55 81.79 57.31 27.57 78.30 54.86 29.80 74.11 51.93 32.47 72.42 50.74 33.54 69.63 48.79 35.32 24.0°C 91.39 73.42 22.27 88.50 71.89 23.80 85.44 70.28 25.58 82.18 68.57 27.60 78.67 65.64 29.83 74.46 62.13 32.51 72.76 60.71 33.58 69.96 58.37 35.36 16.0°C 26.7°C 91.72 84.51 22.30 88.92 82.94 23.83 85.94 81.23 25.61 82.89 79.13 27.65 79.35 75.76 29.89 75.11 71.70 32.57 73.39 70.07 33.64 70.56 67.36 35.43...
  • Page 19: Outlines & Dimensions

    UAT-C_(i) Outlines & Dimensions Outlines & Dimensions Model: UAT150C Model: UAT180C...
  • Page 20 Outlines & Dimensions UAT-C_(i) Model: UAT240C Model: UAT300C...
  • Page 21: Wiring Diagrams

    UAT-C_(i) Wiring Diagrams Wiring Diagrams Model: UAT150C (Mechanical Control)
  • Page 22 Wiring Diagrams UAT-C_(i) Model: UAT150C (Wired Control)
  • Page 23 UAT-C_(i) Wiring Diagrams Model: UAT180C (Mechanical Control)
  • Page 24 Wiring Diagrams UAT-C_(i) Model: UAT180C (Wired Control)
  • Page 25 UAT-C_(i) Wiring Diagrams Model: UAT240C (Mechanical Control)
  • Page 26 Wiring Diagrams UAT-C_(i) Model: UAT240C (Wired Control)
  • Page 27 UAT-C_(i) Wiring Diagrams Model: UAT300C (Mechanical Control)
  • Page 28 Wiring Diagrams UAT-C_(i) Model: UAT300C (Wired Control)
  • Page 29: Installation

    UAT-C_(i) Installation Installation Installation Guideline Safety Precautions This manual provides the procedures of installation to ensure a safe and good standard of operation for the air conditioner unit. Special adjustment may be necessary to suit local requirements. Before using your air conditioner, please read this instruction manual carefully and keep it for future reference. This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use by lay persons.
  • Page 30: Installation Clearances

    Installation UAT-C_(i) Installation Clearances Refer diagram below for the space required around the unit. Note that: a) All dimensions shown are in mm. b) All space values shown are minimum clearance required for the unit. c) Unit shown in the diagram is UAT300C. Other models shall follow the same clearance...
  • Page 31: Specifi Cation Guide

    UAT-C_(i) Specifi cation Guide Specifi cation Guide General Features Condenser Fan & Motor The rooftop unit shall consist of compressors, fan Condenser Motor shall be of IP55 insulation class motors, condenser coils, evaporator coil, expansion rating and is equipped with dust proof bearing. valves, refrigerant piping and electrical components.
  • Page 32: Engineering & Physical Data (Arabic)

    T-C_(i) ‫ﺍﻟﺘﺼﻤﻴﻢ ﺍﻟﻬﻨﺪﺳﻲ ﻭﺍﻟﺒﻴﺎﻧﺎﺕ ﺍﻟﻤﺎﺩﻳﺔ‬ Specifi cation Guide ART-C_(i) ‫ﺍﻟﺘﺼﻤﻴﻢ ﺍﻟﻬﻨﺪﺳﻲ ﻭﺍﻟﺒﻴﺎﻧﺎﺕ ﺍﳌﺎﺩﻳﺔ‬ R22 ‫ﺑﻴﺎﻧﺎﺕ ﻫﻨﺪﺳﻴﺔ – ﺍﻟﻄﺮﺍﺯ‬ T300C T240C T180C T150C ‫ﺍﻟﻄﺮﺍﺯ‬ ‫ﻭﺣﺪﺓ ﺣﺮﺍﺭﻳﺔ‬ 314300 255000 192300 150000 ‫ﺑﺮﻳﻄﺎﻧﻴﺔ / ﺳﺎﻋﺔ‬ [1] ‫ﺳﻌﺔ ﺍﻟﺘﺒﺮﻳﺪ‬ 92.12 74.74 56.36 43.96 ‫ﻛﻴﻠﻮﻭﺍﺕ‬ ‫ﻭﺣﺪﺓ...
  • Page 33: Specifi Cation Guide (Arabic)

    ‫ﺩﻟﻴﻞ ﺍﻟﻤﻮﺍﺻﻔﺎﺕ‬ T-C_(i) ART-C_(i) Specifi cation Guide ‫ﺩﻟﻴﻞ ﺍﳌﻮﺍﺻﻔﺎﺕ‬ ‫ﻣﺮﻭﺣﺔ ﺍﻟﻤﻜﺜﻒ ﻭﺍﻟﻤﻮﺗﻮﺭ‬ ‫ﺍﻟﻤﻴﺰﺍﺕ ﺍﻟﻌﺎﻣﺔ‬ ‫ ﻛﻤﺎ‬IP55 ‫ﻳﺠﺐ ﺃﻥ ﻳﺤﺼﻞ ﻣﺤﺮﻙ ﺍﻟﻤﻜﺜﻒ ﻋﻠﻰ ﺗﺼﻨﻴﻒ ﻃﺒﻘﺔ ﺍﻟﻌﺰﻝ‬ ‫ﺗﺘﻜﻮﻥ ﻭﺣﺪﺓ ﺍﻟﺴﻘﻒ ﻣﻦ ﺍﻟﻀﻮﺍﻏﻂ ﻭﻣﺤﺮﻛﺎﺕ ﺍﻟﻤﺮﻭﺣﺔ ﻭﻣﻠﻔﺎﺕ ﺍﻟﻤﻜﺜﻒ‬ .‫ﻳﺠﺐ ﺗﺰﻭﻳﺪﻩ ﺑﻤﺤﻤﻞ ﻣﻘﺎﻭﻡ ﻟﻸﺗﺮﺑﺔ‬ .‫ﻭﻣﻠﻔﺎﺕ ﺍﻟﻤﺒﺨﺮ ﻭﺻﻤﺎﻣﺎﺕ ﺍﻟﺘﻮﺳﻴﻊ ﻭﺃﻧﺎﺑﻴﺐ ﺍﻟﺘﺒﺮﻳﺪ ﻭﻣﻜﻮﻧﺎﺕ ﻛﻬﺮﺑﺎﺋﻴﺔ‬ .‫ﻳﺠﺐ...
  • Page 34 Specifi cation Guide ART-C_(i)
  • Page 35 ART-C_(i) Specifi cation Guide...

This manual is also suitable for:

Uat180cUat240cUat300c

Table of Contents