Fitting Of Rain Hoods; Anti-Vibration Mounts - Daikin UATYA-BBAY1 Installation, Use And Maintenance Manual

Rooftop packaged unit
Table of Contents

Advertisement

5.3.2

Fitting of rain hoods

A rain guard can be fitted on the opening for the passage of external air.
Protection is achieved with hoods; the number of elements forming the guard depends on the size of the air passage.
The guard is supplied in a separate kit for fitting by the installer.
In addition to the hoods, the kit includes a protective mesh and self-drilling screws for fixing.
The protective mesh is to be fixed between the guard and the frame of the unit and cover the entire opening.
Use a 6 mm screwdriver with socket to fix it.
To fit correctly:
- Rest the mesh filter against the edge of the external air opening;
- begin fitting from the upper part of the opening;
- using the holes on each element of the guard, secure them to the frame of the unit with the self-drilling screws
provided.
- repeat this operation for all the elements of the guard.
5.3.3

Anti-vibration mounts

In order to reduce vibrations transmitted to the structure, it is advisable to install the unit on rubber or spring anti-
vibration mounts, supplied as an accessory and to be requested when placing the order.
The dimensional diagram with footprint shows the position and load of each anti-vibration mount.
The anti-vibration mounts must be fixed on before positioning the unit on the ground.
To install the anti-vibration mounts, see the instructions attached to the accessory.
When fixing the anti-vibration mounts, the unit should be lifted off the ground by no more than 200 mm
and no parts of the body should be placed under the unit.
5.3.3.1
Rubber anti-vibration mounts
The anti-vibration mount consists of an upper metal bell in which there is a screw for fixing it to the base of the unit.
The anti-vibration mount is fixed to the base through the two holes on the flange. The flange of the anti-vibration
mount bears a number (45,60,70 ShA) that identifies the hardness of the rubber support.
We reserve the right to make changes without any prior notice.
UATYA
4P645202-1
Fig. 5 Rain guard
Fig. 6 Rubber/metal anti-vibration mounts
Translation from original instructions