Features Features Key Features High Energy Efficiency Wide Operating Range In line with the market trend of moving towards high The UATN-C series rooftops are specifically designed to deliver top performance in both standard and high energy efficiency products, the UATN-C series is ambient temperature conditions.
Features Component Features Compressor Condenser Coil High efficiency, low noise, and hermetically sealed Condenser coils are manufactured from seamless SCROLL compressors are used in the UATN-C series inner grooved copper tubes mechanically bonded to to give a better performance. aluminium fins to ensure optimum heat transfer. All coils are tested against leaks by Nitrogen holding All compressors are equipped with an internal at 609psig and highly precise Helium leak test at...
Page 9
Features Refrigerant Circuit Phase Sequential Protection The UATN-C series is designed with the ability to The Phase Sequential Protector is a three phase line operate at partial load depending on the requirement monitor module that protects the unit components of the application. against phase loss, phase reversal and phase unbalance.
Application Information Application Information Operating Range Ensure the operating temperature is in allowance range as stated in diagram below. Cooling The use of your air conditioner outside the range of working temperature and humidity can result in serious failure. Indoor WB temperature (°C) Cooling Operation Range DB: Dry Bulb WB: Wet Bulb...
Application Information Installation Guideline Safety Precautions This manual provides the procedures of installation to ensure a safe and good standard of operation for the air conditioner unit. Special adjustment may be necessary to suit local requirements. Before using your air conditioner, please read this instruction manual carefully and keep it for future reference. This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use by lay persons.
Page 13
Application Information 1) Installation Clearances Refer diagram below for the space required around the unit. Note that: a) All dimensions shown are in mm. b) All space values shown are minimum clearance required for the unit. c) Unit shown in the diagram is UATN210/240C. Other models shall follow the same clearance. Model : UATN60/90C Condenser Evaporator coil &...
Page 14
Application Information Compressor Compressor Compressor Minimum Maximum Maximum Full Load Locked Rotor Model Circuit Amps, Fuse Amps, Continuous Current, Current, MCA (A) MFA (A) Current (A) FLA (A) LRA (A) UATN60C 13.7 20.0 UATN90C 19.2 32.0 UATN120C 15/15 64/64 25.0 32.0 UATN150C 19/19...
Sound Data Sound Data Sound Pressure Level 1/1 Octave Sound Pressure (dB, ref 20μPa) Overall Noise Model (dBA) Criteria 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz UATN60C UATN90C UATN120C UATN150C UATN180C UATN210C UATN240C UATN300C Measuring Location Microphone position: (1) Measurement at open field. (2) For all microphone position, the distance will be from the unit center in 1m horizontal follow by 1m vertical.
Sound Data Sound Power Level 1/1 Octave Sound Power Level (dB) ref 1pW Overall Model (dBA) 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz UATN60C UATN90C UATN120C UATN150C UATN180C UATN210C UATN240C UATN300C Measuring Location Microphone position: (1) Measurement at open field (Inlet + radiated). (2) For microphone at position 1 until 4 and 9, the distance will be 1 meter from the centre of the unit’s surface.
Selection Process Selection Process Drive Package The following are the design requirements for UATN60C unit: Model: UATN60C Supply Air Quantity 2000 External Static Pressure Step 1: From the fan curve (at 2000 CFM), Standard operating system; Internal Static Pressure Step 2: Therefore at 2000 CFM and 180 Pa external static pressure, Total Static Pressure 180 + 115...
Fan Performance Table Fan Performance Table UATN60C External Static Pressure (Pascal) Air Flow (CFM) PO (kW) PO (kW) PO (kW) PO (kW) PO (kW) 1500 0.28 0.31 1050 0.36 1161 0.43 1274 0.51 2000 0.35 1024 0.46 1129 0.57 1232 0.66 1331 0.76...
Page 23
Fan Performance Table UATN120C External Static Pressure (Pascal) Air Flow (CFM) PO (kW) PO (kW) PO (kW) PO (kW) PO (kW) 3300 0.59 0.77 0.92 1.12 4400 0.81 0.93 1.18 1.40 1029 1.63 5300 1.19 1.41 1.64 1.88 1060 2.14 Air Flow (CFM) PO (kW)
Page 24
Fan Performance Table UATN210C External Static Pressure (Pascal) Air Flow (CFM) PO (kW) PO (kW) PO (kW) PO (kW) PO (kW) 5800 1.10 1.35 1.63 1.93 7600 1.58 1.86 2.17 2.18 2.85 9000 2.42 2.73 3.07 3.42 3.80 Air Flow (CFM) PO (kW) PO (kW)
Fan Performance Table Dimensional Data Blower Pulley, Motor Pulley, Pulley Center V belt Motor Blower Dm (mm) Dm (mm) Distance, C (mm) Model Length Quantity Output Power Type Dia (mm) Type Dia (mm) Type Nom Min (mm) (pcs) (kW) UATN60C SPZ 1 140/1610 SPZ 1 100/1210 SPZ 0.75 1430...
Engineering & Physical Data Engineering & Physical Data Engineering Data – R410A Model MODEL UATN60C UATN90C UATN120C UATN150C Btu/h 61,000 90,000 121,500 150,000 COOLING CAPACITY 17.88 26.38 35.61 43.96 TOTAL INPUT POWER (COOLING) 4.52 7.20 9.45 12.00 TOTAL RUNNING CURRENT (COOLING) 8.20 13.50 17.00...
Page 35
Engineering & Physical Data Engineering Data – R410A Model MODEL UATN180C UATN210C UATN240C UATN300C Btu/h 181,000 213,000 241,000 304,000 COOLING CAPACITY 53.05 62.43 70.63 89.10 TOTAL INPUT POWER (COOLING) 14.72 16.90 19.29 24.52 TOTAL RUNNING CURRENT (COOLING) 27.20 33.90 38.70 46.00 3.60 3.69...
Engineering & Physical Data Safety Device MODEL INDOOR UATN60C UATN90C TYPE NC, Auto Reset HIGH PRESSURE OPEN kPa / psi 4140 / 600 SWITCH CLOSE kPa / psi 3310 / 480 TYPE NC, Auto Reset SAFETY DEVICE LOW PRESSURE OPEN kPa / psi 124 / 18 SWITCH...
Outlines & Dimensions Outlines & Dimensions Model: UATN60C Weight of corner(kg) Total weight (kg) 1280 1520 1112 1112 1530 1300 CENTER OF GRAVITY Model: UATN90C Weight of corner(kg) Total weight (kg) 1280 1112 1112 1300 CENTER OF GRAVITY...
Page 46
Outlines & Dimensions Model: UATN120/150C Weight at corner(kg) Total weight Model (kg) UATN120C 145 145 150 150 UATN150C 160 160 165 165 1965 1630 1800 1800 CENTER OF GRAVITY Model: UATN180C Weight at corner(kg) Total weight (kg) 190 190 230 230 1045 1905 7 4 1...
Page 47
Outlines & Dimensions Model: UATN210/240C CENTER OF GRAVITY Model: UATN300C Weight at corner(kg) Total weight (kg) 270 300 280 240 1090 CENTER OF GRAVITY...
Service and Maintenance Service & Maintenance The design concept of the rooftop unit is such that all servicing can be done from the side and back of the unit. Upon removal of side and back panel, all the electrical “terminal box”, fan and motor assembly and compressor are easily accessible.
Page 52
Service and Maintenance MAINTENANCE Service Parts Maintenance Procedure Air Filter - Remove any dust adhering to the filter by using a vacuum cleaner or wash in lukewarm water (below 40°C) with a neutral cleaning detergent. - Rinse the filter well and dry before placing it back onto the unit. - Do not use gasoline, volatile substances or chemicals to clean the filter.
Troubleshooting Troubleshooting When a malfunction of the air conditioner unit is detected, immediately switch off the main power supply before proceeding with the following troubleshooting procedures. The following are common fault conditions and simple troubleshooting tips. If any other fault conditions which are not listed occur, contact your nearest local dealer.
Page 54
Troubleshooting Phase Protector The unit with Scroll Compressor can only rotate in one direction. For this reason, a protective device (phase protector) is fitted to prevent incorrect wiring of the electrical phases. When the three phases are not connect- ed correctly, the phase protector operates, and the unit will not start. This device is located in the control box of the outdoor unit.