Condensate Drain Of The Internal Air Coil; Condensate Drain Of The External Air Coil; Connection To The Humidifier - Daikin UATYA-BFC2Y1 Instructions For Installation, Use And Maintenance Manual

Rooftop packaged unit
Table of Contents

Advertisement

5.4.2

Condensate drain of the internal air coil

The condensate collection tray is provided with a male R 1" threaded pipe for connection.
On the condensate discharge pipe it must be installed a proper syphon in order to avoid that outdoor air may be
blown through it.
It is good practice to make a syphon straight after the connection to the tray.
The pipe draining the condensate must never be connected to waste water drains or run-off water drains, only to
rainwater systems to prevent any foul smelling gases from being sucked back.
5.4.3

Condensate drain of the external air coil

The condensate collection tray is provided with a male R 1" threaded pipe for connection.
The condensate drain of the external air coil can be left free.
Any condensate pipework connected to the unit must be protected from freezing.
5.4.4

Connection to the humidifier

Refer to the section titled "Options and accessories" where a description of the humidifier installation procedure is
given.
Translation from original instructions
Packaged Rooftop
38
Fig. 5 Connection to the condensate collection tray
Fig. 6 Syphon for condensate discharge pipe.
Fig. 7 Connection to the condensate collection tray